Mini Amazon III Series
40
Table 2-7.3: KMF-120 DVN4 cooling capacity
Combination
(%) (Capacity
index)
Outdoor tem
-
perature (°C
DB)
Indoor temperature(°C DB/WB)
DB:20.8,WB:14
DB:23.3,WB:16
DB:25.8,WB:18
DB:27,WB:19
DB:28.2,WB:20
DB:30.7,WB:22
DB:32,WB:24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
130%
-5
10.7
1.77
12.8
2.16
14.8
2.31
15.4
2.40
16.1
2.47
16.5
2.69
16.9
2.71
-2
10.7
1.77
12.8
2.20
14.8
2.31
15.4
2.42
16.1
2.47
16.5
2.72
16.9
2.73
0
10.7
1.80
12.8
2.24
14.8
2.40
15.4
2.55
16.1
2.62
16.5
2.76
16.9
2.77
2
10.7
1.83
12.8
2.24
14.8
2.48
15.4
2.69
16.1
2.65
16.5
2.78
16.9
2.81
4
10.7
1.87
12.8
2.28
14.8
2.56
15.4
2.71
16.1
2.68
16.5
2.82
16.9
2.86
6
10.7
1.91
12.8
2.33
14.8
2.66
15.4
2.73
15.9
2.76
16.3
2.86
16.7
2.88
8
10.7
1.95
12.8
2.38
14.8
2.79
15.4
2.86
15.7
2.85
16.1
2.87
16.5
2.91
10
10.7
1.99
12.8
2.43
14.8
2.89
15.4
2.96
15.6
2.91
15.9
2.92
16.3
3.00
12
10.7
2.03
12.8
2.48
14.8
2.95
15.2
3.00
15.4
2.95
15.7
2.96
16.1
3.02
14
10.7
2.07
12.8
2.53
14.8
3.00
15.0
3.05
15.2
3.00
15.6
3.00
15.9
3.08
16
10.7
2.10
12.8
2.58
14.6
3.04
14.8
3.09
14.9
3.08
15.3
3.05
15.7
3.13
18
10.7
2.14
12.8
2.63
14.4
3.09
14.6
3.10
14.8
3.12
15.2
3.15
15.6
3.18
20
10.7
2.19
12.8
2.80
14.2
3.24
14.4
3.25
14.6
3.27
14.9
3.30
15.3
3.34
21
10.7
2.25
12.8
2.90
14.1
3.31
14.3
3.33
14.5
3.35
14.9
3.38
15.2
3.41
23
10.7
2.41
12.8
3.11
13.9
3.46
14.1
3.48
14.2
3.50
14.6
3.53
15.0
3.57
25
10.7
2.57
12.8
3.33
13.7
3.62
13.9
3.63
14.1
3.66
14.5
3.69
14.9
3.73
27
10.7
2.75
12.8
3.56
13.5
3.77
13.7
3.79
13.9
3.81
14.2
3.85
14.6
3.89
29
10.7
2.93
12.8
3.81
13.3
3.92
13.5
3.94
13.7
3.97
14.1
4.01
14.5
4.05
31
10.7
3.13
12.7
4.03
13.1
4.08
13.3
4.10
13.5
4.12
13.9
4.16
14.2
4.21
33
10.7
3.34
12.5
4.18
12.9
4.23
13.1
4.25
13.3
4.27
13.7
4.32
14.0
4.37
35
10.7
3.56
12.3
4.33
12.7
4.38
12.9
4.41
13.1
4.43
13.5
4.48
13.9
4.53
37
10.7
3.78
12.1
4.49
12.5
4.54
12.7
4.57
12.9
4.59
13.2
4.65
13.6
4.70
39
10.7
4.03
11.9
4.54
12.3
4.69
12.5
4.72
12.7
4.75
13.1
4.80
13.5
4.86
41
10.7
4.24
11.8
4.58
12.2
4.74
12.4
4.77
12.5
4.80
12.9
4.81
12.9
4.91
43
10.7
4.35
11.7
4.60
12.1
4.75
12.3
4.79
12.4
4.80
12.7
4.82
12.8
4.92
45
10.7
4.56
11.6
4.65
12.0
4.79
12.2
4.82
12.2
4.82
12.4
4.84
12.5
5.01
48
10.7
4.72
11.6
4.79
11.8
4.83
12.0
4.86
12.1
4.87
12.0
4.92
12.3
5.03
50
10.6
4.75
11.5
4.82
11.7
4.86
11.7
4.88
12.0
4.90
12.0
4.95
12.1
5.05
52
10.4
4.77
11.3
4.84
11.5
4.88
11.6
4.91
11.9
4.92
11.7
4.96
12.0
5.07
54
10.3
4.80
11.1
4.87
11.3
4.91
11.5
4.94
11.6
4.95
11.6
5.00
11.7
5.11
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is above 43 degrees in cooling mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.
Summary of Contents for KMF-100 DVN4