Mini Amazon III Series
114
4.6 Branch Joints
Notes for installers
Use U-shaped branch joints as specified on the
construction drawings – do not replace U-shaped branch
joints with tee joints.
Indoor branch joints may be installed either horizontally
or vertically. Horizontal branch joints must be installed at
an angle to the horizontal not exceeding 10° in order to
avoid uneven distribution of refrigerant and possible
malfunction. Refer to Figure 3-4.8.
To ensure even distribution of refrigerant, a limitation
is placed on how close branch joints may be installed to
bends, other branch joints and the straight sections of
piping leading to indoor units. Refer to Part 3, 3.6 “Branch
Joints”.
Figure 3-4.8: Branch joint orientation
4.7 Pipe Flushing
4.7.1 Purpose
To remove dust, other particles and moisture, which could cause compressor malfunction if not flushed out before the
system is run, the refrigerant piping should be flushed using nitrogen. As described in Part 3, 4.1.1 “Installation procedure”,
pipe flushing should be performed once the piping connections have been completed with the exception of the final
connections to the indoor units. That is, flushing should be performed once the outdoor units have been connected but
before the indoor units are connected.
Summary of Contents for KMF-100 DVN4
Page 140: ......