55
3.1
HEAT MODE
Enable or disable the heating mode
1
0
1
1
/
3.2
t_T4_FRESH_H
The refresh time of climate related curves for heating
mode
0.5
0.5
6
0.5
hours
3.3
T4HMAX
The maximum ambient operating temperature for heating
mode
25
20
35
1
℃
3.4
T4HMIN
The minimum ambient operating temperature for heating
mode
-15
-25
15
1
℃
3.5
dT1SH
The temperature difference for starting the unit (T1)
5
2
10
1
℃
3.6
dTSH
The temperature difference for starting the unit (Ta)
2
1
10
1
℃
3.8
T1SetH1
The setting temperature 1 of climate related curves for
heating mode
35
25
60
1
℃
3.9
T1SetH2
The setting temperature 2 of climate related curves for
heating mode
28
25
60
1
℃
3.10
T4H1
The ambient temperature 1 of climate related curves for
heating mode
-5
-25
35
1
℃
3.11
T4H2
The ambient temperature 2 of climate related curves for
heating mode
7
-25
35
1
℃
3.12
ZONE1 H-EMISSION
The type of zone1 end for heating mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
1
0
2
1
/
3.13
ZONE2 H-EMISSION
The type of zone2 end for heating mode
:
0=FCU(fan coil
unit)
,
1=RAD.(radiator)
,
2=FLH(floor heating)
2
0
2
1
/
3.14
t_DELAY_PUMP
the time that the compressor has run before starting the
pump.
2
2
20
0.5
MIN
4.1
T4AUTOCMIN
The minimum operating ambient temperature for cooling in
auto mode
25
20
29
1
℃
4.2
T4AUTOHMAX
The maximum operating ambient temperature for heating
in auto mode
17
10
17
1
℃
5.1
WATER FLOW TEMP.
Enable or disable the WATER FLOW TEMP.:0=NON,1=YES
1
0
1
1
/
5.2
ROOM TEMP.
Enable or disable the ROOM TEMP.:0=NON,1=YES
0
0
1
1
/
5.3
DOUBLE ZONE
Enable or disable the ROOM THERMOSTAT DOUBLE
ZONE:0=NON,1=YES
0
0
1
1
/
7.1
dT1_IBH_ON
The temperature difference betw een T1S and T1 for
starting the backup heater.
5
2
10
1
℃
7.2
t_IBH_DELAY
The time that the compressor has run before the first
backup heater turns on
30
15
120
5
MIN
7.3
T4_IBH_ON
The ambient temperature for starting the backup heater
-5
-15
10
1
℃
7.7
IBH_LOCATE
IBH/AHS installation location PIPE LOOP=0; BUFFER TANK=1
0
0
0
0
℃
7.8
P_IBH1
Power input of IBH1
0
0
20
0.5
kW
7.9
P_IBH2
Power input of IBH2
0
0
20
0.5
kW
7.10
P_TBH
Power input of TBH
2
0
20
0.5
kW
7.4
dT1_AHS_ON
The temperature difference betw een T1S and T1B for
turning the additional heating source on
5
2
10
1
℃
7.5
t_AHS_DELAY
The time that the compressor has run before starting the
additional heating source
30
5
120
5
MIN
7.6
T4_AHS_ON
The ambient temperature for starting the additional
heating source
-5
-15
10
1
℃
8.1
T1S_H.A_H
The target outlet w ater temperature for space heating
w hen in holiday aw ay mode
25
20
25
1
℃
8.2
T5S_H.A_DHW
The target outlet w ater temperature for domestic hot
w ater heating w hen in holiday aw ay mode
25
20
25
1
℃
12.1
PREHEATING FOR
FLOOR T1S
The setting temperature of outlet w ater during first
preheating for floor
25
25
35
1
℃
12.3
t_FIRSTFH
The time last for preheating floor
72
48
96
12
HOUR
The style of room thermostat
:
0=NON,1=MODE
SET,2=ONE ZONE,3=DOUBLE ZONE
6.1
ROOM THERMOSTAT
0
0
3
1
/
3.7
t_INTERVAL_HEAT
the start time interval of the compressor in HEAT mode.
5
5
5
MIN
56
12.4
t_DRYUP
The day for w arming up during floor drying up
8
4
15
1
DAY
12.5
t_HIGHPEAK
The continue days in high temperature during floor
drying up
5
3
7
1
DAY
12.6
t_DRYD
The day of dropping temperature during floor drying
up
5
4
15
1
DAY
12.7
T_DRYPEAK
The target peak temperature of w ater flow during
floor drying up
45
30
55
1
°C
12.8
START TIME
The start time of floor drying up
Hour
:
the
present
time(not on
the hour +1,
on the hour
+2)
Minute:00
0:00
23:30
1/30
h/min
12.9
START DATE
The start date of floor drying up
The present
date
1/1/2000
31/12/2099
1/1/2001
d/m/y
13.1
AUTO RESTART
COOL/HEAT MODE
Enable or disable the auto restart cooloing/heating
mode. 0=NON,1=YES
1
0
1
1
/
13.2
AUTO RESTART DHW
MODE
Enable or disable the auto restart DHW mode.
0=NON,1=YES
1
0
1
1
/
14.1
POWER INPUT LIMITATION The type of pow er input limitation, 0=NON,
1~8=TYPE 1~8
0
0
8
1
/
15.1
ON/OFF
(
M1 M2
)
Define the function of the M1M2 sw itch;
0= REMOTE ON/OFF,1= TBH ON/OFF,2= AHS ON/OFF
0
0
2
1
/
15.2
SMART GRID
Enable or disable the SMART GRID;
0=NON,1=YES
0
0
1
1
/
15.3
T1b
(
Tw 2
)
Enable or disable the T1b(Tw 2) ;
0=NON,1=YES
0
0
1
1
/
15.4
Tbt1
Enable or disable the Tbt1;
0=NON,1=YES
0
0
1
1
/
15.5
Tbt2
Enable or disable the Tbt2;
0=NON,1=YES
0
0
1
1
/
15.6
Ta
Enable or disable the Ta;
0=NON,1=YES
0
0
1
1
/
15.7
SOLAR INPUT
Choose the SOLAR INPUT;
0=NON,1=CN18Tsolar,2=CN11SL1SL2
0
0
2
1
/
15.8
F-PIPE LENGTH
Choose the total length of the liquid pipe(F-PIPE
LENGTH);
0=F-PIPE LENGTH
<
10m,1=F-PIPE LENGTH
≥
10m
0
0
1
1
/
15.9
dTbtl
The temperature difference for starting the unit(Tbt2)
15
0
50
1
℃
15.10
RT/Ta_PCB
Enable or disable the RT/Ta_PCB;
0=NON,1=YES
0
0
1
1
/
16.1
PER_START
Start-up percentage of multiple units
10
10
100
10
%
16.2
TIME_ADJUST
Adjustment time of adding and subtracting units
5
1
60
1
MIN
16.3
ADDRESS RESET
Reset the address code of the unit
FF
0
15
1
/
17.1
HMI SET
Choose the HMI;
0=MASTER,1=SLAVE
0
0
1
1
/
17.2
HMI ADDRESS FOR BMS Set the HMI address code for BMS
1
1
16
1
/
133
132