PTX5000 Chassis Grounding Cable and Lug Specifications
To meet safety and electromagnetic interference (EMI) requirements and to ensure proper operation, the
PTX5000 must be adequately grounded before power is connected.
Two pairs of threaded inserts (PEM nuts) are provided on the right rear of the chassis for connecting the
packet transport to earth ground. The top pair of grounding points fits M6 screws (European), and the
bottom pair fits UNC 1/4–20 screws (American). The grounding points are spaced at 0.625-in. (15.86-
mm) centers.
The accessory kit shipped with the PTX5000 includes:
• Two UNC 1/4–20 screws used to secure the grounding cable to the bottom grounding points.
• Depending on your configuration:
• 60-A DC PDU—4-AWG (21.2 mm
2
) cable lugs for connecting DC power and grounding the
PTX5000 (see
• 120-A DC PDU—0-AWG (53 mm
2
) cable lugs for connecting DC power and grounding the
PTX5000 (see
• High Capacity DC PDU—4-AWG (21.2 mm
2
) cable lugs for connecting DC power and grounding
the PTX5000 (see
).
CAUTION: Before device installation begins, a licensed electrician must attach a cable
lug to the grounding cable that you supply. A cable with an incorrectly attached lug can
damage the PTX5000.
NOTE: You must install the PTX5000 in a restricted-access location and ensure that the chassis
is always properly grounded. The PTX5000 has a two-hole protective grounding terminal
provided on the chassis. Under all circumstances, use this grounding connection to ground the
chassis. For AC-powered systems, you must also use the grounding wire in the AC power cord
164
Summary of Contents for PTX5000
Page 1: ...PTX5000 Packet Transport Router Hardware Guide Published 2022 12 04...
Page 59: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 41...
Page 63: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 45...
Page 77: ...High Capacity Delta AC PDU LEDs 66 High Capacity Wye AC PDU 68 59...
Page 78: ...Three Phase Delta AC PDU LEDs Figure 29 on page 61 shows the three phase delta AC PDU LEDs 60...
Page 81: ...Three Phase Wye AC PDU LEDs Figure 30 on page 64 shows the three phase wye AC PDU LEDs 63...
Page 228: ...2 Remove each bracket Figure 81 Removing the Center Mounting Bracket 210...
Page 234: ...8 Move the lift away from the rack 216...
Page 235: ...Figure 83 Loading the PTX5000 onto the Lift 217...
Page 270: ...Figure 119 Connecting 20 A Inputs to a High Capacity Single Phase AC PDU 252...
Page 304: ...Figure 140 Installing the Front Door on a PTX5000 in a Four Post Rack 1 Side panels 2 Door 286...
Page 349: ...6 Discard the air filter Figure 154 Removing a Horizontal Air Filter Tray 331...
Page 352: ...Figure 157 Installing the Horizontal Air Filter 334...
Page 354: ...6 Discard the air filter Figure 158 Removing a Vertical Air Filter Tray 336...
Page 357: ...Figure 161 Installing a Vertical Air Filter Tray 339...
Page 428: ...Figure 216 Connecting 20 A Inputs to High Capacity Single Phase AC PDU 410...
Page 429: ...Figure 217 Connecting 30 A inputs to High Capacity Single Phase AC PDU 411...
Page 447: ...8 Insert the input power tray into the PDU Figure 228 Installing a 60 A Input Power Tray 429...
Page 448: ...Figure 229 60 A DC Input Power Terminals 430...
Page 531: ...Figure 276 Do Not Carry an FPC with Only One Hand 513...
Page 584: ...5 CHAPTER Troubleshooting Hardware Troubleshooting PTX5000 Components 567...
Page 651: ...6 CHAPTER Returning the Chassis or Components Returning the PTX5000 Chassis or Components 634...
Page 662: ...Figure 303 FPC2 PTX P1A Serial Number Label 644...
Page 663: ...Figure 304 FPC3 PTX U2 and FPC3 PTX U3 Serial Number Label 645...
Page 669: ...Figure 309 DC PDU Serial Number Label 651...
Page 670: ...Figure 310 AC PDU Serial Number Label 652...