background image

 

 

TLC3-FCR Engineering Manual

 

 

Doc: 70-00-0198, V3.0 Date: 20120403 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

 
TLC3-FCR  
Intelligent Fan Coil Controller 

Features 

 

The PWM control option reduces room temperature 

fluctuations and energy consumption 

 

Low power energy consumption: < 1W per unit 

 

Temperature control for 2-pipe fan coil systems.  

 

Automatic fan control for three stage fans.  

 

Cost saving option with Economy functionality and set point 

limitations 

 

Control for single stage heating, cooling and fan only 

operation modes 

 

Password protected programmable user and control 

parameters 

o

 

Setpoint range limitation 

o

 

Access control for setpoints, fan speeds and mode 

change 

o

 

Access control for heat/cool change and time 

programs 

o

 

Select your display contents 

o

 

Selectable behavior after return from power failure 

 

Temperature display in Celsius or Fahrenheit 

Deluxe Version: 

 

Clock and time schedule functions with power failure protection 

 

Blue backlight for LCD 

 

Infrared remote controller option:  

With special features for Boost and delayed switching on or off 

Applications 

 

Air Only Systems: Three stage fans for single duct systems with up to one binary output for auxiliary heating 

and cooling devices. 

 

Air/Water Systems: Induction units, fan coil units for 2-pipe systems with one binary output for a spring 

return valve.  

General Description 

The TLC3-FCR is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR features 1 internal 

NTC temperature sensor and four binary outputs (Relays).  
A detailed parameterization is possible with the use of a simple configuration routine. The TLC3-FCR can be configured 

using the standard operation terminal. No special tools or software is required.  

Ordering 

Item Name 

Item code 

Variant 

Power 

Features 

TLC3-FCR-24 

TLC3-FCR-24-W01 

40-10 0128 
40-10 0128-01 

Standard 

Cooling only 

24VAC/DC 

Fan coil controller with:  
1 TI internal 

3 DO (Relay) Fan control 
1 DO (Relay) Binary valve control 

TLC3-FCR-230 

TLC3-FCR-230-W01 

40-10 0110 
40-10 0110-01 

Standard 

Cooling only 

230VAC 

TLC3-FCR-D-24 
TLC3-FCR-D-24-W01 

40-10 0133 
40-10 0133-01 

Deluxe 
Cooling only 

24VAC/DC 

TLC3-FCR-D-230 

TLC3-FCR-D-230-W01 

40-10 0111 
40-10 0111-01 

Deluxe 

Cooling only 

230VAC 

Selection of actuators and fans 

Binary auxiliary devices: E.g. fans, on/off valves, etc.  Do not directly connect devices that exceed 2(1.2)A. Observe 

startup current on inductive loads! Do not connect more than one fan coil unit to one controller. 

Summary of Contents for TLC3-FCR

Page 1: ...ngle duct systems with up to one binary output for auxiliary heating and cooling devices Air Water Systems Induction units fan coil units for 2 pipe systems with one binary output for a spring return valve General Description The TLC3 FCR is a stand alone electronic fan coil controller with one control loop The TLC3 FCR features 1 internal NTC temperature sensor and four binary outputs Relays A de...

Page 2: ...3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls EN 60 730 1 EN 60 730 2 9 Electromagnetic compatibility for domestic sector Emissions EN 60 730 1 Immunit...

Page 3: ... 2 off the surface of the mounting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight ...

Page 4: ...kup function to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Error me...

Page 5: ... d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One bar on the right side indicates the first switching event Press UP DOWN to select action for first switching event No switching event not active OFF switches unit off Reset UP17 active if switched to ON...

Page 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to change stale...

Page 7: ...oints ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time programs ON OFF ON Enabled UP 05 State after power failure 0 Switched OFF 1 Switched ON 2 state before power failure 0 1 2 2 UP 06 Enable Economy unoccupied Mode Shift the set point to a lower temperature ...

Page 8: ...on in cooling mode 0 10 0 C 20 0 F 1 0 C 2 F FC 07 Switching Hysteresis is the difference between switching on and switching off A small hysteresis will increase the number of switching cycles and thus the wear on fan and relays contacts 0 10 0 C 20 0 F 0 5 C 1 F FC 08 Mold Protection In mold protection the fan keeps running independent of temperature as long as the unit is switched on ON OFF OFF ...