Vector TLC3-FCR Engineering Manual Download Page 6

 

 

TLC3-FCR Engineering Manual

 

 

Doc: 70-00-0198, V3.0 Date: 20120403 

© Vector Controls GmbH, Switzerland 

Page 6 

Subject to alteration 

Operation with OPR-1 

The deluxe version may be alternatively operated with an infrared remote 

controller.  
 
1.

 

Mode indication, Auto, Dry, Cool, Fan, Heat 

2.

 

2-digit display of setpoint 

3.

 

Fan indication 

4.

 

4-digit display of current time or delayed switching time 

5.

 

Economy button: Toggles Economy/Comfort mode 

6.

 

Mode button, changes operation modes 

7.

 

UP/DOWN Button: Set point adjustment buttons 

8.

 

FAN Button: Changes fan speed, low – medium – high or Auto 

9.

 

Boost button, activates full output for 5 Minutes 

10.

 

Time related buttons: Timer, Hour, Minute 

11.

 

POWER Button: Operation mode ON – OFF 

Switching ON 

The unit is switched on by pressing the POWER button. It will start up in comfort 

mode. 

Changing between COMFORT and ECONOMY 

Pressing the SLEEP button toggles between ECONOMY and COMFORT modes.  

Switching OFF 

Pressing the POWER while the unit is on, will switch the unit off. The current time will be displayed in the LCD of OPR-1.  

Changing of set points 

Only the set points for the temperature loop may be changed. Set point range is 15 to 30 °C. 

Changing of fan speeds 

Repeatedly pressing the fan speed button steps through low, medium, high and automatic fan speeds. Automatic fan 

speed will not be activated in FAN ONLY mode.  

Boost 

Pressing the boost button activates a 5 minute boost. The output will be fully opened for the period of 5 minutes 
independent of demand. This may be used to change stale air during a meeting break or when entering the room.  

Clock settings 

The remote controller contains a daytime clock. In order to set the clock, press HOUR and MINUTE button together 

until the clock starts blinking. Then set the correct time with the HOUR and MINUTE buttons. Confirm by pressing the 

TIMER button.  The clock of the OPR will set the clock of the controller.  

Delayed switching 

The unit may be delayed switched on or off using the timer button. Pressing the timer button once will display Timer 

ON if currently in OFF mode or TIMER OFF if currently in ON mode. Set the time when the unit is supposed to switch 

on or off using the HOUR and MINUTE buttons.  

Mode changes 

Repeatedly pressing the mode button may activate the following operation modes: HEAT, COOL and FAN ONLY. The 

mode change may be disabled using the UP parameters. 
 
Note:  
The remote controller is currently only available in °C mode.  

 

 

 

 

 

 

 

 

 

 

11 

Summary of Contents for TLC3-FCR

Page 1: ...ngle duct systems with up to one binary output for auxiliary heating and cooling devices Air Water Systems Induction units fan coil units for 2 pipe systems with one binary output for a spring return valve General Description The TLC3 FCR is a stand alone electronic fan coil controller with one control loop The TLC3 FCR features 1 internal NTC temperature sensor and four binary outputs Relays A de...

Page 2: ...3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls EN 60 730 1 EN 60 730 2 9 Electromagnetic compatibility for domestic sector Emissions EN 60 730 1 Immunit...

Page 3: ... 2 off the surface of the mounting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight ...

Page 4: ...kup function to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Error me...

Page 5: ... d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One bar on the right side indicates the first switching event Press UP DOWN to select action for first switching event No switching event not active OFF switches unit off Reset UP17 active if switched to ON...

Page 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to change stale...

Page 7: ...oints ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time programs ON OFF ON Enabled UP 05 State after power failure 0 Switched OFF 1 Switched ON 2 state before power failure 0 1 2 2 UP 06 Enable Economy unoccupied Mode Shift the set point to a lower temperature ...

Page 8: ...on in cooling mode 0 10 0 C 20 0 F 1 0 C 2 F FC 07 Switching Hysteresis is the difference between switching on and switching off A small hysteresis will increase the number of switching cycles and thus the wear on fan and relays contacts 0 10 0 C 20 0 F 0 5 C 1 F FC 08 Mold Protection In mold protection the fan keeps running independent of temperature as long as the unit is switched on ON OFF OFF ...

Reviews: