Vector TLC3-FCR Engineering Manual Download Page 2

 

 

TLC3-FCR Engineering Manual

 

 

Doc: 70-00-0198, V3.0 Date: 20120403 

© Vector Controls GmbH, Switzerland 

Page 2 

Subject to alteration 

Technical Specification 

Power Supply 

Operating Voltage 

-24 

-230 

 

AC voltage: 50/60Hz 

22-26V AC/DC 

210

–250 VAC 

 

Power Consumption 

Max 1W, 1.5 VA 

 

Electrical Connection 

Terminal Connectors 

 

Deluxe type only: 
Power backup for real time clock 

 
Min 48h if charged for 24h 

Signal Inputs 

Temperature Inputs 

Range 
Accuracy 

Internal 
0…50 °C (32…122 °F) 
0.5°C (1°F) 

Signal Outputs 

Digital Switching Outputs 

Switching Type 
AC Switching power 

Insulation strength 

between relays contacts and system electronics: 
between neighboring relays contacts 

DO1 to DO4 
Relays 
0…250V AC 2A max. each output 

 

3750V AC to EN 60 730-1 
1250V AC to EN 60 730-1 

Environment 

Operation 

Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0°C 

…50°C (32°F…122°F) 

<95% R.H. non-condensing 

 

Transport & Storage 

Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25

°C…70°C (-13°F…158°F) 

<95% R.H. non-condensing 
class 2M2 

Standards 

conformity 
EMC Directive 
Low Voltage Directive 

2004/108/EC 
2006/95/EC 

 

Product standards 

Automatic electrical controls for household and similar use 
Special requirement on temperature dependent controls 

 
EN 60 730 

–1 

EN 60 730 

– 2 - 9 

 

Electromagnetic compatibility for  
domestic sector 

Emissions: EN 60 730-1 
Immunity: EN 60 730-1 

 

Degree of Protection 

IP30 to EN 60 529 

 

Pollution Class 

II (EN 60 730-1) 

 

Safety Class:  

for -24 types 
for -120 and -230 types 

III (IEC 60 536)  
II (IEC 60 536) 

 

Overvoltage Category:  

for -24 types 
for 120 and -230 types 

I (EN 60 730-1) 
III (EN 60 730-1) 

General 

Dimensions (H x W x D) 

Front part: 21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.)  
Power case: 60 x 50 x 32mm (2.4 x 2.0 x 1.3 in) 

 

Material: Cover, back part 
Mounting Plate 

ABS plastic (UL94 class V-0) 
Galvanized Steel 

 

Weight (including package) for -24 types 

for -230 types 

standard: 265g (9.3oz), deluxe: 275g (9.7oz) 
standard: 295g (10.5oz), deluxe: 305g (10.8oz) 

 Dimensions 

 

 

88 (3.5) 

32 (1.2) 

8

8

 (

3

.5

21  

(0.8) 

Space required in flush mounting box: 

(H x W x D)  

60 x 50 x 32mm (2.4 x 2.0 x 1.26 in.) 
 
Distance for mounting screws: 
Horizontal and vertical:  

45 to 63mm (1.8 to 2.5 in.) 
 

Summary of Contents for TLC3-FCR

Page 1: ...ngle duct systems with up to one binary output for auxiliary heating and cooling devices Air Water Systems Induction units fan coil units for 2 pipe systems with one binary output for a spring return valve General Description The TLC3 FCR is a stand alone electronic fan coil controller with one control loop The TLC3 FCR features 1 internal NTC temperature sensor and four binary outputs Relays A de...

Page 2: ...3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automatic electrical controls for household and similar use Special requirement on temperature dependent controls EN 60 730 1 EN 60 730 2 9 Electromagnetic compatibility for domestic sector Emissions EN 60 730 1 Immunit...

Page 3: ... 2 off the surface of the mounting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight ...

Page 4: ...kup function to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection display will remain until a button is pressed Frost protection can be enabled disabled using user parameter UP 09 Error me...

Page 5: ... d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One bar on the right side indicates the first switching event Press UP DOWN to select action for first switching event No switching event not active OFF switches unit off Reset UP17 active if switched to ON...

Page 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to change stale...

Page 7: ...oints ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time programs ON OFF ON Enabled UP 05 State after power failure 0 Switched OFF 1 Switched ON 2 state before power failure 0 1 2 2 UP 06 Enable Economy unoccupied Mode Shift the set point to a lower temperature ...

Page 8: ...on in cooling mode 0 10 0 C 20 0 F 1 0 C 2 F FC 07 Switching Hysteresis is the difference between switching on and switching off A small hysteresis will increase the number of switching cycles and thus the wear on fan and relays contacts 0 10 0 C 20 0 F 0 5 C 1 F FC 08 Mold Protection In mold protection the fan keeps running independent of temperature as long as the unit is switched on ON OFF OFF ...