• PTX5000 AC and DC high capacity PSM efficiency is approximately 90% at full load and nominal
voltage.
The examples below show the power requirement calculations for different types of configurations:
NOTE: All the examples below use RE-PTX-X8-64G Routing Engines, CB2-PTX Control Boards,
FAN3-PTX-H horizontal fan trays, and SIB3-PTX5K SIBs.
• This example shows the calculation for a non-redundant base configuration with no FPCs or PICs at
25° C (77° F) ambient temperature:
1 host sub 1 vertical fan tray + 2 horizontal fan trays + SIBs = output power in watts
182 W + 80 W + 2(330 W) + 1170 W = 2092 W
Output power in watts / power supply efficiency = power consumption in watts
2092 W / 0.9 = 2324.4 W
• This example shows the calculation for a redundant base configuration with four FPC3-PTX-U3 FPCs
and eight P3-15-U-QSFP28 PICs at 25° C (77° F) ambient temperature:
2 host subs 1 vertical fan tray + 2 horizontal fan trays + SIBs + 4 FPC3-PTX-U3 FPCs
+ 8 P3-15-U-QSFP28 PICs = output power in watts
2(182 W) + 80 W + 2(330 W) + 1170 W + 4(754 W) + 8(119 W) = 6242 W
Output power in watts / power supply efficiency = power consumption in watts
6242 W / 0.9 = 6935.6 W
• This example shows the calculation for a redundant base configuration with eight FPC3-PTX-U3
FPCs and sixteen P3-15-U-QSFP28 PICs at 40° C (104° F) ambient temperature:
2 host subs 1 vertical fan tray + 2 horizontal fan trays + SIBs + 8 FPC3-PTX-U3 FPCs
+ 16 P3-15-U-QSFP28 PICs = output power in watts
2(187 W) + 370 W + 2(900 W) + 1170 W + 8(777 W) + 16(123 W) = 11898 W
181
Summary of Contents for PTX5000
Page 1: ...PTX5000 Packet Transport Router Hardware Guide Published 2022 12 04...
Page 59: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 41...
Page 63: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 45...
Page 77: ...High Capacity Delta AC PDU LEDs 66 High Capacity Wye AC PDU 68 59...
Page 78: ...Three Phase Delta AC PDU LEDs Figure 29 on page 61 shows the three phase delta AC PDU LEDs 60...
Page 81: ...Three Phase Wye AC PDU LEDs Figure 30 on page 64 shows the three phase wye AC PDU LEDs 63...
Page 228: ...2 Remove each bracket Figure 81 Removing the Center Mounting Bracket 210...
Page 234: ...8 Move the lift away from the rack 216...
Page 235: ...Figure 83 Loading the PTX5000 onto the Lift 217...
Page 270: ...Figure 119 Connecting 20 A Inputs to a High Capacity Single Phase AC PDU 252...
Page 304: ...Figure 140 Installing the Front Door on a PTX5000 in a Four Post Rack 1 Side panels 2 Door 286...
Page 349: ...6 Discard the air filter Figure 154 Removing a Horizontal Air Filter Tray 331...
Page 352: ...Figure 157 Installing the Horizontal Air Filter 334...
Page 354: ...6 Discard the air filter Figure 158 Removing a Vertical Air Filter Tray 336...
Page 357: ...Figure 161 Installing a Vertical Air Filter Tray 339...
Page 428: ...Figure 216 Connecting 20 A Inputs to High Capacity Single Phase AC PDU 410...
Page 429: ...Figure 217 Connecting 30 A inputs to High Capacity Single Phase AC PDU 411...
Page 447: ...8 Insert the input power tray into the PDU Figure 228 Installing a 60 A Input Power Tray 429...
Page 448: ...Figure 229 60 A DC Input Power Terminals 430...
Page 531: ...Figure 276 Do Not Carry an FPC with Only One Hand 513...
Page 584: ...5 CHAPTER Troubleshooting Hardware Troubleshooting PTX5000 Components 567...
Page 651: ...6 CHAPTER Returning the Chassis or Components Returning the PTX5000 Chassis or Components 634...
Page 662: ...Figure 303 FPC2 PTX P1A Serial Number Label 644...
Page 663: ...Figure 304 FPC3 PTX U2 and FPC3 PTX U3 Serial Number Label 645...
Page 669: ...Figure 309 DC PDU Serial Number Label 651...
Page 670: ...Figure 310 AC PDU Serial Number Label 652...