Table 90: Troubleshooting PSM Chassis Alarms
(Continued)
Alarm
Type
LCD Display
Message
CLI Message
Alarm Condition
Solution
PSM
psm-
number Absent
PSM
psm-number
Absent
The PSM is not installed.
NOTE: This alarm is
generated by the following
Junos OS Releases:
12.1X48 12.3, and 13.2R1.
Junos OS Release 13.2R2
and later does not generate
this alarm.
If a required PSM is missing, install
the PSM.
If PSMs are not missing and you
continue to get the alarm, you can
install Junos OS Release 13.2R2 or
later.
Pwr Mgmt Non
Op
Power Manager
Non
Operational
Different types of PSMs are
present in the chassis.
NOTE: Zoning and
nonzoning PSMs might be
present.
Install the same type of PSMs in each
slot.
RELATED DOCUMENTATION
PTX5000 AC Power Distribution Unit LEDs | 58
PTX5000 DC Power Distribution Unit LEDs | 99
PTX5000 AC Power Supply Module LEDs | 70
PTX5000 DC Power Supply Module LEDs | 105
Troubleshooting the PTX5000 Host Subsystem
IN THIS SECTION
605
Summary of Contents for PTX5000
Page 1: ...PTX5000 Packet Transport Router Hardware Guide Published 2022 12 04...
Page 59: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 41...
Page 63: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 45...
Page 77: ...High Capacity Delta AC PDU LEDs 66 High Capacity Wye AC PDU 68 59...
Page 78: ...Three Phase Delta AC PDU LEDs Figure 29 on page 61 shows the three phase delta AC PDU LEDs 60...
Page 81: ...Three Phase Wye AC PDU LEDs Figure 30 on page 64 shows the three phase wye AC PDU LEDs 63...
Page 228: ...2 Remove each bracket Figure 81 Removing the Center Mounting Bracket 210...
Page 234: ...8 Move the lift away from the rack 216...
Page 235: ...Figure 83 Loading the PTX5000 onto the Lift 217...
Page 270: ...Figure 119 Connecting 20 A Inputs to a High Capacity Single Phase AC PDU 252...
Page 304: ...Figure 140 Installing the Front Door on a PTX5000 in a Four Post Rack 1 Side panels 2 Door 286...
Page 349: ...6 Discard the air filter Figure 154 Removing a Horizontal Air Filter Tray 331...
Page 352: ...Figure 157 Installing the Horizontal Air Filter 334...
Page 354: ...6 Discard the air filter Figure 158 Removing a Vertical Air Filter Tray 336...
Page 357: ...Figure 161 Installing a Vertical Air Filter Tray 339...
Page 428: ...Figure 216 Connecting 20 A Inputs to High Capacity Single Phase AC PDU 410...
Page 429: ...Figure 217 Connecting 30 A inputs to High Capacity Single Phase AC PDU 411...
Page 447: ...8 Insert the input power tray into the PDU Figure 228 Installing a 60 A Input Power Tray 429...
Page 448: ...Figure 229 60 A DC Input Power Terminals 430...
Page 531: ...Figure 276 Do Not Carry an FPC with Only One Hand 513...
Page 584: ...5 CHAPTER Troubleshooting Hardware Troubleshooting PTX5000 Components 567...
Page 651: ...6 CHAPTER Returning the Chassis or Components Returning the PTX5000 Chassis or Components 634...
Page 662: ...Figure 303 FPC2 PTX P1A Serial Number Label 644...
Page 663: ...Figure 304 FPC3 PTX U2 and FPC3 PTX U3 Serial Number Label 645...
Page 669: ...Figure 309 DC PDU Serial Number Label 651...
Page 670: ...Figure 310 AC PDU Serial Number Label 652...