• A 23-in. rack using appropriate 23-in. to 19-in. rack adapters and an appropriate installation shelf
which supports the chassis at the correct vertical position to properly line up the rack mount holes.
Juniper Networks does not supply this hardware, but consideration for the size and weight of the
chassis is important for a safe installation. Juniper recommends the use of single-sided panel
adapters of at least 10 U in height, using as many as needed to fully overlap the chassis rack mount
bracket for this type of installation.
The rack rails must be spaced widely enough to accommodate the chassis's external dimensions: 62.5 in.
(158.8 cm) high, 33.1 in. (84.1 cm) deep, and 17.5 in. (44.5 cm) wide. The outer edges of the mounting
brackets extend the width to 19 in. (48.3 cm). The front cable management system adds 3.8 in. (9.7 cm)
to the depth. If the front door is used, this adds 5.5 in. (14 cm) to the depth of the chassis. The rear cable
management system adds 5.5 in. (14 cm) to the depth of the chassis.
The spacing of rails and adjacent racks must also allow for the clearances around the chassis and rack
that are specified in
"PTX5000 Clearance Requirements for Airflow and Hardware Maintenance" on
For instructions about installing the mounting hardware, see
"Installing the PTX5000 Mounting
Hardware for a Four-Post Rack or Cabinet" on page 206
The chassis height of 62.5 in. (158.8 cm) high is approximately 35.7 U. A U is the standard rack unit
defined in
Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D) published
by the Electronics Industry Association. You can install one chassis in a rack that has at least 35.7 U of
usable vertical space.
The rack must be strong enough to support the weight of the fully configured PTX5000, up to about
1,200 lb (544.3 kg).
175
Summary of Contents for PTX5000
Page 1: ...PTX5000 Packet Transport Router Hardware Guide Published 2022 12 04...
Page 59: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 41...
Page 63: ...NOTE The PDUs contain no fans but are cooled by the fans in the power supply modules 45...
Page 77: ...High Capacity Delta AC PDU LEDs 66 High Capacity Wye AC PDU 68 59...
Page 78: ...Three Phase Delta AC PDU LEDs Figure 29 on page 61 shows the three phase delta AC PDU LEDs 60...
Page 81: ...Three Phase Wye AC PDU LEDs Figure 30 on page 64 shows the three phase wye AC PDU LEDs 63...
Page 228: ...2 Remove each bracket Figure 81 Removing the Center Mounting Bracket 210...
Page 234: ...8 Move the lift away from the rack 216...
Page 235: ...Figure 83 Loading the PTX5000 onto the Lift 217...
Page 270: ...Figure 119 Connecting 20 A Inputs to a High Capacity Single Phase AC PDU 252...
Page 304: ...Figure 140 Installing the Front Door on a PTX5000 in a Four Post Rack 1 Side panels 2 Door 286...
Page 349: ...6 Discard the air filter Figure 154 Removing a Horizontal Air Filter Tray 331...
Page 352: ...Figure 157 Installing the Horizontal Air Filter 334...
Page 354: ...6 Discard the air filter Figure 158 Removing a Vertical Air Filter Tray 336...
Page 357: ...Figure 161 Installing a Vertical Air Filter Tray 339...
Page 428: ...Figure 216 Connecting 20 A Inputs to High Capacity Single Phase AC PDU 410...
Page 429: ...Figure 217 Connecting 30 A inputs to High Capacity Single Phase AC PDU 411...
Page 447: ...8 Insert the input power tray into the PDU Figure 228 Installing a 60 A Input Power Tray 429...
Page 448: ...Figure 229 60 A DC Input Power Terminals 430...
Page 531: ...Figure 276 Do Not Carry an FPC with Only One Hand 513...
Page 584: ...5 CHAPTER Troubleshooting Hardware Troubleshooting PTX5000 Components 567...
Page 651: ...6 CHAPTER Returning the Chassis or Components Returning the PTX5000 Chassis or Components 634...
Page 662: ...Figure 303 FPC2 PTX P1A Serial Number Label 644...
Page 663: ...Figure 304 FPC3 PTX U2 and FPC3 PTX U3 Serial Number Label 645...
Page 669: ...Figure 309 DC PDU Serial Number Label 651...
Page 670: ...Figure 310 AC PDU Serial Number Label 652...