15
1 Introduction
1.7.2
Modules
The proven input and output modules are available as module variants (type 7050xx; incl. controller
module).
For example: the analog input module with universal inputs for thermocouples, RTD temperature probes,
and voltage or current standard signals. As a result the same hardware can be used to precisely acquire
and digitize a highly diverse range of process variables.
JUMO variTRON 300 enables simultaneous operation of up to 32 control loops so that it can also be
used for sophisticated processes. Through expansion slots the inputs and outputs of each controller
module can be individually expanded and adapted. The control loops here operate fully independently,
which means they do not require resources from the central processing unit.
Thyristor power controllers can also be connected via EtherCAT or PROFINET. In addition, JUMO dig-
iLine sensors for liquid analysis can be connected to the central processing unit.
Wireless transmission of measured values
As of system version 5, the central processing unit JUMO variTRON 300 is also available with a wireless
interface that enables wireless transmission of measured values. The transmitters of the JUMO Wtrans
series are available as measuring probes (Wtrans T, Wtrans B, Wtrans p). A maximum of 32 transmitters
can be operated on the central processing unit.
During startup, the display of the RSSI value (Received Signal Strength Indicator) in the Web Cockpit is
helpful as an indicator of the signal strength of a received radio telegram.
Input/output modules
Module designation
Data sheet
Features
Multichannel controller module 705010
•
Up to 4 independently configurable PID control
loops with a fast cycle time and proven control
algorithms
•
Independent operation
•
Math and logic functions
•
Counter input up to 10 kHz
Relay module 4-channel
705015
•
4 relay outputs controlled via the system bus
by digital signals
•
Changeover contact in each case (230 V / 3 A)
•
Switching statuses are displayed with LEDs
Analog input module
4-channel
705020
•
4 high-quality, configurable analog inputs for
RTD temperature probes, resistance transmit-
ters, thermocouples, current 0(4) to 20 mA,
voltage 0(2) to 10 V
•
All inputs are galvanically isolated from each
other
•
Customer-specific linearization possible
•
Limit value monitoring
•
Additional digital input
Analog input module
8-channel
705021
•
8 high-quality analog inputs for RTD tempera-
ture probes Pt100, Pt500, Pt1000 in two-wire
circuit
•
Limit value monitoring
•
Additional digital input
Analog output module
4-channel
705025
•
4 configurable analog outputs 0(4) to 20 mA or
0(2) to 10 V
•
Adjustable output behavior in case of malfunc-
tion
Summary of Contents for 705003
Page 2: ......
Page 6: ...Contents...
Page 20: ...1 Introduction 20...
Page 25: ...25 2 Mounting 2 3 Dimensions 101 110 5 45 94 5 101 5 17 5...
Page 26: ...2 Mounting 26...
Page 68: ...4 Operation 68 The files are available for download in the web browser click on the file...
Page 94: ...5 Configuration 94...
Page 98: ...6 Startup 98...
Page 109: ...109 7 Annex 7 5 China RoHS...
Page 110: ...7 Annex 110...