107
7 Annex
System states and errors
The following table lists all the system states and errors that are indicated by the "S" LED (module-de-
pendent).
The web application (service) and the setup program (hardware configuration) must be used for further
diagnosis and, if necessary, measures.
Category
"S" LED
(Status)
Meaning
Diagnos-
tics with
Recommended action
Start error
Module error (hardware does not
start up)
LED
Replace module
Start error
Internal error (bootloader)
Various errors during startup (e.g. no
memory, initialization error)
LED
Replace module
Start error
No firmware
LED
Replace module
Start error
Incorrect optional board 1, 2, 3
(actual/target)
LED
Check optional board and
replace, load, or remove as
required; replace module if
necessary
Bus status
No connection to central processing
unit
LED
Check whether the central pro-
cessing unit is running; check
cabling and topology
Bus status
System in "Stop" (INIT) state – no
error, only in start phase
LED
Bus status
System in "Stop" (PREOP) state – no
error, only in start phase
LED
Operation
(Priority 1)
Module not calibrated (LED flashes
red-green) or
module in calibration mode (cali-
brate/test; LED flickers red-green)
LED/setup
program
Operation
(Priority 2)
Collective alarm (incl. out of range)
LED/setup
program
Operation
(Priority 3)
System in "Stop" (SAFEOP) state –
no error
LED
Operation
(Priority 3)
System in "Run" (OP) state – no
error
LED
Summary of Contents for 705003
Page 2: ......
Page 6: ...Contents...
Page 20: ...1 Introduction 20...
Page 25: ...25 2 Mounting 2 3 Dimensions 101 110 5 45 94 5 101 5 17 5...
Page 26: ...2 Mounting 26...
Page 68: ...4 Operation 68 The files are available for download in the web browser click on the file...
Page 94: ...5 Configuration 94...
Page 98: ...6 Startup 98...
Page 109: ...109 7 Annex 7 5 China RoHS...
Page 110: ...7 Annex 110...
Page 111: ......