6-8
SM-18003
FIELD WORK INSTRUCTIONS
6.6 Service and Maintenance Record
Service and Maintenance Record
No.
Check Item
Action
Judgment
1
Is service space sufficient?
YES or NO
2
Short Circuit of Discharged Air?
YES or NO
3
Any Heat Influence?
YES or NO
4
Is ground wiring connected?
YES or NO
5
Refrigeration Piping
GOOD or NOT GOOD
6
Fixing of Units
GOOD or NOT GOOD
7
Any Damage on External or Internal
Surface?
YES or NO
8
Checking of Screws and Bolts
Tighten them if they are loosened.
TIGHTENED or
NOT TIGHTENED
9
Tightening of Terminal Screws
Tighten all terminal screws with a
Phillips screwdriver.
TIGHTENED or
NOT TIGHTENED
10
Are compressor terminals
tightly fixed?
Check all compressor terminals are
tightly fixed.
GOOD or NOT GOOD
11 Insulation Resistance
Measure insulation resistance with
insulation resistance-meter.
Comp. and Fan
Motor: greater than 3M
W
Others: greater than 3M
W
GOOD or NOT GOOD
12
Does condensate water smoothly flow?
Check for smooth flow by
pouring water.
GOOD or NOT GOOD
13
Check for leakage at compressor.
Check for any leakage.
GOOD or NOT GOOD
14
Check for leakage at
outdoor heat exchanger.
Check for any leakage.
GOOD or NOT GOOD
15 Check for leakage at
indoor heat exchanger.
Check for any leakage.
GOOD or NOT GOOD
16
Check for leakage at reversing valve.
Check for any leakage.
GOOD or NOT GOOD
17
Check for leakage at check valve.
Check for any leakage.
GOOD or NOT GOOD
18
Check for leakage at accumulator.
Check for any leakage.
GOOD or NOT GOOD
19
Check for leakage at strainer.
Check for any leakage.
GOOD or NOT GOOD
20
Check for leakage at
electronic expansion valve.
Check for any leakage.
GOOD or NOT GOOD
21
Check for leakage at piping.
Check for any leakage.
GOOD or NOT GOOD
22
Check direction of fans.
by Viewing or Airflow Volume
GOOD or NOT GOOD
23
Voltage among each phase.
Check the voltage is within
the specified range.
GOOD or NOT GOOD
24
Vibration and Sound
Check fan, compressor, piping.
GOOD or NOT GOOD
25 Activation of Each Operation Mode
Check activation of COOL,
HEAT, STOP and TEMP. switches.
GOOD or NOT GOOD
26
High Pressure Cut-out Switch
Check actual activation value.
GOOD or NOT GOOD
27
Check activation of drain-up mechanism.
Check it during cooling operation.
GOOD or NOT GOOD
28
Indoor Inlet Air Temp. (DB/WB)
o
F DB/
o
F WB
29
Indoor Outlet Air Temp. (DB/WB)
o
F DB/
o
F WB
30
Outdoor Inlet Air Temp. (DB/WB)
o
F DB/
o
F WB
31
Outdoor Outlet Air Temp. (DB/WB)
o
F DB/
o
F WB
32
High Pressure Sensor
psi(G)
33
Low Pressure Sensor
psi(G)
34
Operating Voltage
V
35 Operating Current
A
36
Instruction for Cleaning of Air Filter to Client
DONE or NOT YET
37 Instruction for Cleaning Method to Client
DONE or NOT YET
38
Instruction for Operation to Client
DONE or NOT YET
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...