5-30
SM-18003
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(64) Cooling Lower Limit for Setting Temperature (FC)
This function is utilized to limit the lowest setting temperature for FAN/COOL/DRY operations.
When this function is valid, it provides the appropriate cooling operation and energy saving.
The setting conditions and the minimum setting temperature for cooling are as follows:
<Example>
(65) Heating Upper Limit for Setting Temperature (Fd)
This function is utilized to limit the highest setting temperature for HEAT operation.
When this function is valid, it provides the appropriate heating operation and energy saving.
The setting conditions and the heating upper limit for the setting temperature are as follows:
<Example>
Setting Condition
Details
Minimum Setting Temperature
(FAN/COOL/DRY) *
00
Standard Value
66
o
F (19
o
C)
01
Lower Limit +2
o
F (Lower Limit +1
o
C)
68
o
F (20
o
C)
02
Lower Limit +4
o
F (Lower Limit +2
o
C)
70
o
F (21
o
C)
03
Lower Limit +6
o
F (Lower Limit +3
o
C)
72
o
F (22
o
C)
04
Lower Limit +8
o
F (Lower Limit +4
o
C)
74
o
F (23
o
C)
05
Lower Limit +10
o
F (Lower Limit +5
o
C)
76
o
F (24
o
C)
06
Lower Limit +11
o
F (Lower Limit +6
o
C)
77
o
F (25
o
C)
07
Lower Limit +12
o
F (Lower Limit +7
o
C)
78
o
F (26
o
C)
08
Lower Limit +14
o
F (Lower Limit +8
o
C)
80
o
F (27
o
C)
09
Lower Limit +16
o
F (Lower Limit +9
o
C)
82
o
F (28
o
C)
10
Lower Limit +18
o
F (Lower Limit +10
o
C)
84
o
F (29
o
C)
* In case of Standard Unit
Setting Condition
Details
Setting Temperature Upper Limit
(HEAT) *
00
Standard Value
86
o
F (30
o
C)
01
Upper Limit -2
o
F (Upper Limit -1
o
C)
84
o
F (29
o
C)
02
Upper Limit -4
o
F (Upper Limit -2
o
C)
82
o
F (28
o
C)
03
Upper Limit -6
o
F (Upper Limit -3
o
C)
80
o
F (27
o
C)
04
Upper Limit -8
o
F (Upper Limit -4
o
C)
78
o
F (26
o
C)
05
Upper Limit -9
o
F (Upper Limit -5
o
C)
77
o
F (25
o
C)
06
Upper Limit -10
o
F (Upper Limit -6
o
C)
76
o
F (24
o
C)
07
Upper Limit -12
o
F (Upper Limit -7
o
C)
74
o
F (23
o
C)
08
Upper Limit -14
o
F (Upper Limit -8
o
C)
72
o
F (22
o
C)
09
Upper Limit -16
o
F (Upper Limit -9
o
C)
70
o
F (21
o
C)
10
Upper Limit -18
o
F (Upper Limit -10
o
C)
68
o
F (20
o
C)
11
Upper Limit -20
o
F (Upper Limit -11
o
C)
66
o
F (19
o
C)
12
Upper Limit -22
o
F (Upper Limit -12
o
C)
64
o
F (18
o
C)
* In case of Standard Unit
Factory-Setting: "00"
(Lower Limit 66+0=66
o
F (19+0=19
o
C))
Setting Condition: "06"
(Lower Limit 66+11=77
o
F (19+6=25
o
C))
66
o
F
(19
o
C)
86
o
F
(30
o
C)
86
o
F
(30
o
C)
77
o
F
(25
o
C)
Temperature Setting: Available
Setting Temperature at Wired Controller
Temperature Setting
: Not Available
Temperature Setting
: Available
Factory-Setting: "00"
(Upper Limit 86-0=86
o
F (30-0=30
o
C))
Setting Condition: "09"
(Upper Limit 86-16=70
o
F (30-9=21
o
C))
64
o
F
(18
o
C)
86
o
F
(30
o
C)
64
o
F
(18
o
C)
70
o
F
(21
o
C)
Setting Temperature at Wired Controller
Temperature Setting: Available
Temperature Setting
: Not Available
Temperature Setting
: Available
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...