SM-18003
3-19
TROUBLESHOOTING
1: Refer to Section 3.1.4 (3) above for details.
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Activation of
Float Switch
Failure of
Float Switch
Failure of
Drain Pump
Contact Failure
Incorrect Connection
Failure
Contact Failure
Incorrect Connection
Failure
Check drain pan.
Check drainage by
pouring water.
Check continuity
when drain level is low.
Measure resistance
with a tester.
Measure resistance
with a tester.
Measure voltage
between CN36 terminals
with a tester.
Check connection.
Check connection.
High Drain
Level
Clogging of
Drainage
Up-Slope
Drain Piping
Remove foreign particles
clogging drain pipe.
Replace float switch
if faulty.
Replace drain pump
if faulty.
Replace and tighten
connector.
Replace and tighten
connector.
Repair connection.
Repair connection.
Check PCB in
Self-Checking Mode.
1
Replace it if faulty.
Failure of Indoor Unit PCB
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...