SM-18003
5-29
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(58) Automatic Reset Temperature for Heating (F6)
This function is utilized to set the automatic reset temperature for HEAT operation.
The setting conditions and the automatic reset temperature for heating are as follows:
(59) Operation Stoppage Prevention by Wired Controller Operational Error (F7)
This function is utilized to prevent the accidental operational stoppage caused by inadvertently
pressing (ON/OFF) on the wired controller. When this function is valid, the operation is stopped by
pressing “ ” (ON/OFF) button on the wired controller for more than 3 seconds. However, the enabling
method is not changed.
Operation Lock (60) to (63)
Four operation lock functions are available as shown below.
These functions are utilized to restrict each switch operation from the wired controller.
When these functions are valid, modification of each function is prohibited.
All operation lock functions are valid (“01” setting) before shipment.
Each switch operation becomes unavailable by pressing “ ” and “Back/Help” (return) buttons
simultaneously for more than 3 seconds when these functions are set as “01”. The indication “
” (operation
lock indicator) is indicated on the wired controller. If “ ” and “Back/Help” (return) switches are pressed
simultaneously for more than 3 seconds during “ ” (operation lock indicator) is indicated, “
” indication
is turned OFF and each switch operation is available. These functions are to restrict the operations of
the wired controller only. If operation is preformed from the centralized controller, the command from the
centralized controller is given priority.
(60) Lock Function for Operation Mode Selection (F8)
(61) Lock Function for Temperature Setting (F9)
(62) Lock Function for Fan Speed Selection (FA)
(63) Lock Function for Swing Louver Operation (Fb)
Setting Condition
Setting Temperature for Automatic Reset
62 (17)
62
o
F (17
o
C)
64 (18)
64
o
F (18
o
C)
66 (19)
66
o
F (19
o
C)
68 (20)
68
o
F (20
o
C)
70 (21)
70
o
F (21
o
C) (Factory-Setting)
72 (22)
72
o
F (22
o
C)
74 (23)
74
o
F (23
o
C)
76 (24)
76
o
F (24
o
C)
77 (25)
77
o
F (25
o
C)
78 (26)
78
o
F (26
o
C)
80 (27)
80
o
F (27
o
C)
82 (28)
82
o
F (28
o
C)
84 (29)
84
o
F (29
o
C)
86 (30)
86
o
F (30
o
C)
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...