EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.4.1.2 Power Supply ON/OFF 1 (Automatic Operation When Power Supply Is ON)
This function is utilized to run/stop the unit by turning ON/OFF the power supply. When this function
is utilized in the condition that there is no person to operate the unit, monitor the system for disaster
prevention. When using this function, refer to Section 5.4.2.2 "(30) Power Supply ON/OFF (Automatic
Operation
When Power Supply Is ON) (d1)" for the setting.
NOTE:
1. The unit will be stopped even when the power supply is turned ON/OFF due to power failure. If power
failure occurs during the stoppage of the unit, the operation is restarted after the power supply is
restored.
2. Wired Controller is required for this function.
3. When the communication cable is not used in the twin, triple and quad combinations for simultaneous
operation, set this function only to the main indoor unit.
5.4.1.3 Power Supply ON/OFF 2 (Restarting Function After Power Failure)
This function is utilized to restart the unit operation automatically when the power supply is restored after
the power failure over 2 seconds. In case of the power failure for 2 seconds or less, the standard unit
memorize all the operation mode and restarts the operation automatically. (The compressor restarts
operation after 3 minutes guard in addition to power failure time for up to 2 seconds.)
When this function is utilized in the condition that there is no person to operate the unit, monitor the system
for disaster prevention. When using this function, refer to Section 5.4.2.2 "(32) Power Supply ON/OFF
(Restarting Function after Power Failure) (d3)" for setting.
NOTE:
1. If power failure occurs during the stoppage of the unit, the unit remains stopped after the power supply is
restored.
2. Wired Controller is required to be connected for setting this function.
3. When the communication cable is not used in the twin, triple and quad combinations for simultaneous
operation, set this function only to the main indoor unit.
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...