SM-18003
5-19
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
56
F4
Automatic Reset Time
×
00
01
02
03
30 min. (Factory-Setting)
15 min.
60 min.
90 min.
57
F5
Automatic Reset Temperature
for Cooling (*3)
×
66 (19)
68 (20)
70 (21)
72 (22)
74 (23)
76 (24)
77 (25)
78 (26)
80 (27)
82 (28)
84 (29)
86 (30)
66
o
F (19
o
C)
68
o
F (20
o
C)
70
o
F (21
o
C)
72
o
F (22
o
C)
74
o
F (23
o
C)
76
o
F (24
o
C)
77
o
F (25
o
C) (Factory-Setting)
78
o
F (26
o
C)
80
o
F (27
o
C)
82
o
F (28
o
C)
84
o
F (29
o
C)
86
o
F (30
o
C)
58
F6
Automatic Reset Temperature
for Heating (*4)
×
62 (17)
64 (18)
66 (19)
68 (20)
70 (21)
72 (22)
74 (23)
76 (24)
77 (25)
78 (26)
80 (27)
82 (28)
84 (29)
86 (30)
62
o
F (17
o
C)
64
o
F (18
o
C)
66
o
F (19
o
C)
68
o
F (20
o
C)
70
o
F (21
o
C) (Factory-Setting)
72
o
F (22
o
C)
74
o
F (23
o
C)
76
o
F (24
o
C)
77
o
F (25
o
C)
78
o
F (26
o
C)
80
o
F (27
o
C)
82
o
F (28
o
C)
84
o
F (29
o
C)
86
o
F (30
o
C)
59
F7
Operation Stoppage Prevention by
Wired Controller Operational Error
(*5)
×
00
01
Not Available
Available
60
F8
Lock Function for Operation Mode
Selection
×
00
01
Not Available
Available (Factory-Setting)
61
F9
Lock Function for Temperature
Setting
×
00
01
Not Available
Available (Factory-Setting)
62
FA
Lock Function for Fan Speed
Selection
×
00
01
Not Available
Available (Factory-Setting)
63
Fb Lock Function for Swing Louver
Operation
×
00
01
Not Available
Available (Factory-Setting)
64
FC Cooling Lower Limit for Setting
Temperature (*3)
×
00
01
02
03
04
05
06
07
08
09
10
66
o
F (19
o
C)
68
o
F (20
o
C)
70
o
F (21
o
C)
72
o
F (22
o
C)
74
o
F (23
o
C)
76
o
F (24
o
C)
77
o
F (25
o
C)
78
o
F (26
o
C)
80
o
F (27
o
C)
82
o
F (28
o
C)
84
o
F (29
o
C)
65
Fd
Heating Upper Limit for Setting
Temperature (*4)
×
00
01
02
03
04
05
06
07
08
09
10
11
12
86
o
F (30
o
C)
84
o
F (29
o
C)
82
o
F (28
o
C)
80
o
F (27
o
C)
78
o
F (26
o
C)
77
o
F (25
o
C)
76
o
F (24
o
C)
74
o
F (23
o
C)
72
o
F (22
o
C)
70
o
F (21
o
C)
68
o
F (20
o
C)
66
o
F (19
o
C)
64
o
F (18
o
C)
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...