SM-18003
3-49
TROUBLESHOOTING
3.4.2 Test Run from Outdoor Unit Side
Refer to the Service Manual for Outdoor Unit.
3.4.3 Checking the Test Run
(1) Indoor and Outdoor Fan
Check that the indoor fan and outdoor fan
rotate correctly and the airflow is smooth.
(2) Power Supply Voltage
Check the power supply.
If the power supply is abnormal, contact the electric
power company.
Usually, voltage drop will occur when starting the operation as shown in the figure (V
2
).
In order to protect the device, comply with the following normal range of the power supply voltage.
<Normal Range of Power Supply Voltage>
• Supply Voltage: Rated Voltage < +10%
Operating Voltage (V
3
): Rated Voltage < +10%
• Starting Voltage (V
2
): Rated Voltage > -15%
Voltage Imbalance between Phase: < 3%
(3) Normal Operating Pressure
Normal operating suction pressure is 29 to 159.5 psi (0.2 to 1.1 MPa) and normal operating discharge
pressure is 145 to 507.6 psi (1.0 to 3.5 MPa) when the refrigerant charge quantity is correct. Check
the operation pressure in the test run mode.
(4) High Pressure Switch
Check the operation pressure of the high pressure switch in the table below.
(5) High Pressure Increase Retry (Protection Control)
(a) High pressure will increase when one of the following procedures is performed.
Refrigerant
Operation Pressure
R410A
601 psi (4.15MPa)
Initial Voltage
< Voltage Change >
(V
1
)
Starting Voltage
(V
2
)
Operating Voltage
(V
3
)
Cover the air inlet of outdoor unit
during cooling operation.
Cover the air inlet of indoor unit
during heating operation.
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...