SM-18003
5-25
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(22) Thermistor of Wired Controller (C8)
This function is utilized to control the unit by the built-in thermistor of the wired controller (wired
controller thermistor) instead of the inlet air thermistor.
Set this function at “01” or “02” when utilizing this function.
However, even if this function is set at “01” or “02”, if the detecting temperature is abnormal due to the
failure of the thermistor of the wired controller, etc., the control is changed to the inlet air thermistor of
the indoor unit automatically.
The optional part Remote Sensor (THM-R2A) will control the unit when it is connected.
(30) Power Supply ON/OFF 1 (Automatic Operation when Power Supply Is ON) (d1)
This function is utilized to run/stop the unit by turning ON/OFF the power supply.
When this function is utilized in the condition that there is no person to operate the unit, monitor the
system for potential unit failure.
NOTE:
The unit will be stopped even when the power supply is turned ON/OFF due to power failure. If power
failure occurs during the stoppage of the unit, the operation is restarted after the power supply is
restored.
(31) Not Prepared (d2)
(26) Not Prepared (CC)
(27) Not Prepared (Cd)
(28) Not Prepared (CE)
(29) Change of Louver Swing Angle (CF)
This function is utilized to the change louver swing angle.
Setting
Condition
Louver Swing Angle
(Air Discharge Angle)
Purpose
00
7 Steps
Standard Operation
01
Lower 2 Steps are Cut
Draft Prevention
02
Higher 2 Steps are Cut
For High Ceiling
NOTE:
When changing the setting, turn OFF the power supply or
allow the louver to make one complete swing fully in the auto
swing mode to validate the setting.
Setting
Condition
Logic of
Contact
Sequence
Activation
00
A Contact
Normal
Forced
Stoppage
01
B Contact
Normal
Forced
Stoppage
Contact "Close"
Contact "Open"
Indoor
PCB
Indoor
PCB
Air
Discharge
Angle
(23) Not Prepared (C9)
(24) Not Prepared (CA)
(25) Selection of Forced Stoppage Logic (Cb)
This function is utilized to select the logic of the contact for forced stoppage signal input.
The setting condition and the logic of the contact are as shown below.
Selected Thermistor
Setting Condition
Controlled Indoor Temp.
Thermistor of Wired Controller
00
Indoor Suction Thermistor
01
Thermistor of Wired Controller
02
Average Value of Indoor Suction Thermistor and
Thermistor of Wired Controller
Remote Sensor
00
Average Value of Indoor Suction Thermistor and
Remote Sensor
01
Remote Sensor
02
Same as "00"
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...