5-12
SM-18003
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
5.4.1.4 Control by Field-Supplied Room Thermostat
[ Input Setting: Code (01) (for Cooling), Code (02) (for Heating) ]
In a case where a field-supplied room thermostat is used instead of the inlet thermistor of the indoor unit in
order to run/stop the compressor, connect wires as shown below.
Operation
Cooling Operation: Compressor is ON by closing terminals 2 and 3 of CN3
Compressor is OFF by opening terminals 2 and 3 of CN3
Heating Operation: Compressor is ON by closing terminals 1 and 2 of CN3
Compressor is OFF by opening terminals 1 and 2 of CN3
2
Temperature
Increase
Thermostat
CN3
3
2
1
3
1
Indoor Unit PCB
3P Connector
Field-Supplied Room Thermostat
Example: Room Thermostat Input (for Cooling) is set to terminals 2 and 3 of CN3
Room Thermostat Input (for Heating) is set to terminals 1 and 2 of CN3
NOTE:
The contact capacity of a thermostat
shall be DC12V and several mA. Select a
thermostat which makes and breaks the
contact with this capacity.
( )
NOTE:
1. Make the wires CN3 as short as possible. Do not install the wires along the 220V power line. Install
them more than 12 in. (30cm) away from each other. (Intersecting them is acceptable.)
If the wires are installed along the power line, comply with the following points to prevent noise.
a. Pass either of the low voltage wire and 220V power line through a metal tube and ground one end.
b. Use a shielded wire for a low voltage wire and ground one end.
The maximum wiring length is 230 ft. (70m).
2. When using this function, it is recommended that safety devices such as an electric leakage breaker or
smoke detector, etc., be used because this is an unattended function.
3. For a thermostat, do not use a thermostat which uses mercury for a switch, because chattering is likely to
occur at ON/OFF.
4. Use a thermostat with a differential of 2
o
F (1.5
o
C) or more.
5. Comply with the following points. If not, a high-voltage circuit breaker will be activated or the unit will
repeat ON/OFF operation.
a. Install a thermostat where air inlet temperature can be detected correctly.
b. Install a thermostat where discharge air from the unit does not blow directly against it.
6. When using a room thermostat, set each room thermostat (for cooling and heating) correctly. If any of
them is set incorrectly, other room thermostats do not operate.
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...