3-50
SM-18003
TROUBLESHOOTING
3.4.4 Check List for Refrigerant System
Refer to the Service Manual for Outdoor Unit.
3.4.5 Reset for Accumulated Operation Time of Compressor 1-2 (cUJ1- cUJ2)
Refer to the Service Manual for Outdoor Unit.
(b) When the high pressure retry control is activated, alarm code “
” will be indicated on the
7-segment display of the outdoor unit PCB. If the high pressure retry control occurs three times or
more within 30 minutes, alarm code “
” will be indicated on the LCD of the wired controller or the
7-segment display of the outdoor unit PCB.
NOTE:
High pressure may not increase until the high pressure switch is activated because of the
temperature condition.
< For CIW01 >
Sel.
OP MODE
I.U.
: RCI-3.0FSN3
MODEL : F .02
Alarm Code:
22
O.U.
: RAS-3HVRNM2
01-02
AlarmRst
Address
Entr
IDU
: ******
ODU : ******
Chek
OK
Summary of Contents for CICM008B21S
Page 2: ......
Page 10: ...viii SM 18003 ...
Page 15: ...SM 18003 1 1 INSTALLATION 1 Installation ...
Page 19: ...SM 18003 2 1 OPERATION 2 Operation ...
Page 20: ...2 2 SM 18003 OPERATION 2 1 Indoor Unit Refer to the Operation Manual for Mini Cassette ...
Page 22: ......
Page 23: ...SM 18003 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 73: ...MAINTENANCE SM 18003 4 1 4 Maintenance ...
Page 138: ......
Page 139: ...SM 18003 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 148: ...6 10 SM 18003 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b ...
Page 149: ...SERVICE PARTS LIST SM 18003 7 1 7 Service Parts List ...
Page 150: ...SERVICE PARTS LIST 7 2 SM 18003 Refer to the Service Parts List for Mini Cassette ...
Page 151: ......
Page 152: ... 2018 Johnson Controls Inc SM 18003 Code No LIT 12013034 Issued April 2018 ...