13.4 Phase sequence
Verify the direction of the rotating field voltage in
the measured value display of the device.
·Normally a “right” rotation field exists.
UL1-UL2-UL3 = right rotation field
UL1-UL3-UL2 = left rotation field
Fig.
IllustratFon of the phase sequence accordFni to
the rotatFon field dFrectFong.
To do this, open the menu screen “
PoFnter
dFairam
”:
·If you are
not
in the measured value display
“
OvervFew
”, switch to this view by pressing key
1 (Esc) several times.
·Press key 1 (Esc) to open the main menu.
·With keys 3 (
) and 4 (
) select “Pointer
diagram” and confirm your selection with key 6
(Enter).
Fig.
MaFn menu,
“PoFnter dFairam” selectFon
13.5 Frequency
The device requires the rated or power frequency
to measure and calculate measured values,
which can either be specified by the user or
automatically determined by the device.
NOTE
The UMG 96-PA
MID
only supports automatic
frequency calculation (45 -65 Hz)!
·To determine power frequency, a voltage
greater than 20 V
eff
(4-conductor measurement)
or a voltage L1-L2 greater than 34 V
eff
(3-conductor measurement) must be present at
voltage measurement input V1.
·The power frequency must be within the range
of 45 to 65 Hz.
·If the applied voltage is not sufficiently high, the
device will be unable to determine the power
frequency and thus will also not be able to
conduct a measurement.
More information can be found in chap. „12.3.1
Rated frequency“ on page 35