www.janitza.com
UMG 96-PA
/
UMG 96-PA
MID
65
14.6 Log
The log
·records password changes and changes in
current and voltage transformer ratios (CT and
VT).
·records a maximum of 48 changes with the
recording of the respective meter reading.
·Can be reached in the MID window by pressing
key 6.
NOTE
The device blocks password configurations
after 48 entries in the log.
14.7 Password configuration
The configuration of your device can be blocked
with a password.
You will need the password to make any change
in the device configuration.
NOTE
·Note your password and keep it in a safe
place!
·You can only configure your device with
a password! Contact Janitza support if you
lose the password!
·The
MID device
is configured ex works with
the password
10000
.
·For legal reasons, password protection cannot
be disable on the
MID device
.
·After the password is entered incorrectly four
times, the device blocks the configuration for
15 minutes.
Setting range: 10000 - 99999
Standard setting:
10000 (MID device)
Instructions on setting the password are provided
in chap. „Setting the password:“ on page 39.
An additional protective measure consists
of blocking the device for 15 minutes after
incorrectly entering the password three times.
14.8 Measured value display tariff
NOTE
The UMG 96-PA
MID
features software-controlled
tariffs that are not
MID-compliant
.
For non-compliant tariffs, the following symbol
appears in the
TarFff
screen of the MID device:
Fig.
DFsplay total (L1g.g.L3) of the actFve, reactFve and apparent
eneriy on the MID devFce accordFni to software-
controlled tarFff (not calFbrated - )g.
14.9 Device acceptance report
During installation and work on the
MID device
,
the person working on the device must ensure
that a device acceptance report is obtained up
or, if necessary, that entries are supplemented!
The device acceptance report contains
information on current and voltage transformer
types and their settings (converter ratios, dates
and times).
NOTE
·During the entire service life of the MID device,
the device acceptance certificate must be
stored safely and kept available!
·Create, check and/or complete entries of
the converter configurations in the device
acceptance report!