10. Analog Output
The device has one passive analog output
that can output a current of 0 - 20 mA. An
external power adapter (24 V DC) is required for
operation.
The connectable load must not exceed
a resistant of 300 ohm.
If the analog output is loaded with a higher
resistance, the output range (20 mA) is limited.
The measured value assigned to the analog
output, the start and end values and the output
range
4 - 20 mA
or
0 - 20 mA
must be set via the
GridVis® software (more information can be found
in chapter „13.13 Analog output“ on page 56)
230 V AC
24 V DC
+
-
26
25
Analog output 1
+
Analog inputs
UMG 96-PA
External operating
voltage
+
-
=
Fig.