www.janitza.com
UMG 96-PA
/
UMG 96-PA
MID
17
5. Assembly
5.1 Installation location
The device is suitable for indoor installation in
a stationary and weather-protected switch board.
Ground conductive switchboards!
5.2 Installation position
The cut-out size in the switchboard is
92
+0.8
mm x 92
+0.8
mm.
Keep the following minimum distances to ensure
sufficient ventilation:
Fig.
Rear vFew of FnstallatFon posFtFon of UMG 96-PA
5.3 Fastening
Fasten the device using the side mounting
brackets inside the switchboard (mounting plate).
To this end, take the following steps:
·Before inserting the device, remove the
mounting brackets by applying horizontal lever
movement (with a screw driver, for example).
Fig.
SFde vFew of UMG 96-PA
wFth mountFni bracketsg.
Mounting plate
Tensioning screw
Screwdriver
Mounting
bracket
If the tightening screws touch the mounting plate
apply no more than 2 additional turns to mount
the device
·Guide your device from the front through the
switchboard (mounting plate).
·Fasten the brackets on the side of the device
by inserting and snapping them in.
·Screw in the tensioning screws until they touch
the mounting plate.
·The, apply two additional turns and carefully
tighten the tightening screws. Tensioning
screws that are tightened too firmly may
destroy the mounting brackets!
NOTE
UMG 96-PA
MID
:
Observe the additional
information about assembly in section 14.2 on
page 63.
ATTENTION
Property damage due to noncompliance with
the assembly instructions!
Non-observance of the assembly instructions
may damage or destroy your device.
·
Observe the information for the installation
location in the “Assembly” and “Technical
data” sections.
·
Ensure sufficient air circulation in your
installation environment and, where
applicable, sufficient cooling with high
temperatures!