13.7 Checking the power measurement
Short circuit all current transformer outputs
except for one and verify the powers displayed.
·The device may only display one power in the
phase with the current transformer output that
is not short circuited.
·If this is not the case, verify the connections
of the measured voltage and the measured
current.
If the value of the active power is correct, but the
sign is negative, this can have two causes:
1. Reversed connections S1(k) and S2(l) on the
current transformer, or
2. Active energy is being fed back into the
network.
Pull up the pointer diagram with details about the
power:
·If you are
not
in the measured value display
“
OvervFew
”, switch to this view by pressing key
1 (Esc) several times.
·Press key 1 (Esc) to open the main menu.
·With keys 3 (
) and 4 (
) select “
PoFnter
dFairam
” and confirm your selection with key 6
(Enter).
13.8 Checking the communication
The device counts all received (RX), all
transmitted (TX) and all faulty data packages.
Ideally, the number of faults shown in the Faults
column equals 0.
·If you are
not
in the measured value display
“
OvervFew
”, switch to this view by pressing key
1 (Esc) several times.
·Press key 1 (Esc) to open the main menu.
·Using keys 3 (
) and 4 (
) select “
System
”
from the main menu.
·Confirm using key 6 (Enter).
·Using keys 3 (
) and 4 (
) select the submenu
“Overview COMports” and confirm with key 6
(Enter).
Pulling up main menu:
·If you are in the view “
OvervFew COMports
” pull
up the submenu with key 1 (Esc).
·Press key 1 (Esc) again to pull up the main
menu.
·Select the desired measured value display with
keys 3 (
) and 4 (
) . Confirm the selection
with key 6 (Enter) or navigate directly to the
measured value display
“OvervFew”
by pressing
key 1 (Esc).
Fig.
“OvervFew” menu wFth vFew of communFcatFon
parameters (Comg. VFew)g.
Fig.
Illustrated Fn the poFnter dFairam are voltaies wFth
loni poFnters and currents wFth short poFntersg.