13.12 Digital Inputs/Outputs
You device has 3 digital outputs and three digital
inputs.
·You configure the digital inputs and outputs
using the GridVis
®
software.
·You can download the GridVis
®
software from
our website (www.janitza.de).
NOTE
The
UMG 96-PA
MID
features limited digital
output configuration!
13.12.1 Digital inputs
From the digital inputs, you send information
from other devices that have a digital output
directly to your device.
In addition, there is also an option to configure
digital inputs as functional inputs (function
mode). As a functional input, each digital input
has its own function. A functional input cannot
be configured as a pulse counter.
From the configuration window of the GridVis
®
software, you can configure digital inputs from
the “
PerFpherals
” area:
unctFon mode
·Function assigned to the digital input.
Pulse counter
·Value type of the arriving signal (such as electric
power, gas/water consumption, CO
2
,...)
·Pulse value for measurement or power values.
·Length of the averaging time.
The states of the digital inputs are each stored
on their own Modbus address.
For each digital input, the last
16 switching activities (incidents) are logged with
a time stamp.
Fig.
ConfiiurFni the dFiFtal Fnputs usFni the GrFdVFs
®
software
Function mode
Each digital input can be assigned a specific
function.
·Digital input 1
Configuration possible as a tariff switch (HT/NT).
·Digital input 2
Configuration to synchronize the device clock
with the option to synchronize to the minute or
to the hour.
The device can also be synchronized from
a Modbus address.
·Digital input 3
Configuration as a reset input for synchronous
value of the trailer pointing function. The trailer
pointer can also be synchronized from the
Modbus address.