18. Technical data
Transport and storage
The following information applies to devices that are transported or stored in the original packaging.
Free fall
1 m
Temperature
-25 °C to +70 °C
Relative humidity (non-condensing)
0 to 90% RH
Ambient conditions during operation
Use the device in a weather-protected, stationary application.
Protection class II in accordance with IEC 60536 (VDE 0106, Part 1).
Measurement temperature range
-10 °C .. +55 °C
Relative humidity (non-condensing)
0 to 75 % RH
Operating altitude
0 .. 2000 m above sea level
Pollution degree
2
Installation position
discretionary
Ventilation
No external ventilation required.
Protection against foreign bodies and water
- Front
- Rear
- Front side with sealing
IP40 i.a.w. EN60529
IP20 i.a.w. EN60529
IP54 according to EN60529 (required for the MID device!)
Supply voltage
230 V option
Nominal range
AC 90 V - 277 V (50/60 Hz) or
DC 90 V - 250 V, 300 V CATIII
Power consumption
max. 4.5 VA / 2 W
24 V option
Nominal range
AC 24 V - 90 V (50/60Hz) or
DC 24 V - 90 V, 150 V CATIII
Power consumption
max. 4.5 VA / 2 W
Operating range
+-10% of nominal range
Internal fuse, not interchangeable
Type T1A / 250 VDC / 277 VAC according to IEC 60127
Recommended overcurrent protection device for the line
protection (approval according to UL)
230 V option: 6 - 16 A (Char. B)
24 V option: 1 - 6 A (Char. B)
Recommendation for the maximum number of devices on one circuit breaker:
230 V option: Circuit breaker B6A: 4 devices max. / circuit breaker B16A: 11 devices max.
24 V option: Circuit breaker B6A: 3 devices max. / circuit breaker B16A: 9 devices max.
General information
Net weight (with attached connectors)
Approx. 250 g
Packaging weight (including accessories)
Approx. 500 g
Battery
Type Lithium CR2032, 3 V (approval according to UL 1642)
Service life of the background lighting
40000 h
(background lighting is reduced to approx. 50% for this period)