UMG 96-PA
/ UMG 96-PA
MID
www.janitza.com
54
Fig.
“Comparators” Fn the “OvervFew/
comparators” menu
2
1
3
4
6
5
Output for comparator group
Two comparator groups (comparator 1 and 2)
are available with 3 comparators each (A - C) to
monitor limit values.
The results of the comparators A to C can be
linked with “
AND
” or “
OR
”.
The linking results of the comparator group
1 can be assigned to digital output 2 and the
linking results of the comparator group 2 can be
assigned to digital output 3.
The comparators are configured exclusively
using the GridVis® software in the configuration
area “
Comparator
”.
Exporting comparator settings at the device:
·Using keys 3 (
) and 4 (
) select “
OvervFew
”
from the main menu.
·Confirm using key 6 (Enter).
·Using keys 3 (
) and 4 (
) select the submenu
“Comparator 1” for comparator group 1 and
“Comparator 2” for comparator group 2.
·Confirm using key 6 (Enter).
1
Actual value
2
Limit value
3
Comparator
4
Comparator duration
5
Logic
6
Status
Fig.
ConfiiurFni the comparators Fn the GrFdVFs
®
software