UMG 96-PA
/
UMG 96-PA
MID
55
Comparator duration
Comparator durations are time counters that add
up for a set comparator output. That is, if the
condition of the comparator has been met and
the lead time has expired, the counter increases
by the relevant time amount - the minimum
switching time is not considered here!
Comparator with set limit violation
·The set limit value is compared with the
measured value.
·If a limit value violation is active at least for the
duration of the lead time, the comparative result
is changed.
·The result remains unchanged at least for the
duration of the minimum switch-on time and no
more than for the duration of the limit violation.
The result is reset once there is no more limit
violation and the minimum switch-on time has
expired.
Measured value
Limit value
Limit violation
(E.g. exceeded)
Lead time
Minimum switch-on
time
Comparative result
Comparator duration
Digital-
ausgang 2
21
23
0/1
Vergleichergruppe 1
Vergleicher A
Vergleicher B
Vergleicher C
Logik
Ergebnis
UMG 96-PA
0/1
Inverter
- nicht invertiert
- invertiert
Display-Anzeige
Status
Fig.
Block dFairam: Use of dFiFtal output 2 for lFmFt value monFtorFni