Service functions and error messages
Page 144
Error message
Meaning of the error message
Measures
Main
index
Sub index
3
DeviceNet: overflow of transmit buffer Reduce the number of message per time unit that are to be
transmitted.
4
DeviceNet: IO send error
Please contact the Technical Support.
5
DeviceNet: bus Off
Check the DeviceNet wiring.
6
DeviceNet:
CAN controller overflow
Please contact the Technical Support.
65
0
DeviceNet: no module
Technology module defective?
Replace the technology module.
1
DeviceNet: I/O connection timeout
Please contact the Technical Support.
72
0
Profinet: Initialization error
Replace the Profinet module.
1
Profinet: Bus error
No communication possible, e.g. because the
bus cable is disconnected. Check the cabling and restart the
Profinet communication.
3
Profinet: Invalid IP configuration
IP address, subnet mask or gateway address are not valid or
not permissible.
Change IP configuration.
4
Profinet: Invalid device name
According to the Profinet standard, the Profinet device name
is not permissible.
Change device name.
5
Profinet: Technology module defect
Replace the Profinet module.
6
Profinet: Invalid / not supported
indication
A Profinet feature has been used that is not supported by the
module.
If necessary, contact the Technical Support.
78
0
NRT frame send error
Reduce bus traffic, for example by using less devices in a
line.
80
0
IRQ:
current controller overflow
Please contact the Technical Support.