Goodrive200A
inverters Function parameters
89
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
fault
processing
1:No alarm and continue to run
2:No alarm and stop according to the stop means
(only under the communication control)
3:No alarm and stop according to the stop means
(under all control modes)
P14.06
Communicati
on
processing
LED ones:
0: Operation with response: the drive will respond
to all reading and writing commands of the upper
monitor.
1:Operation without response
;
The drive only
responds to the reading command other than the
writing command of the drive. The
communication efficiency can be increased by
this method.
LED tens:
0: Communication encrypting valid
1: Communication encrypting invalid
0x00
○
P16 Group Ethernet function
P17 Group Monitoring function
P17.00
Setting
frequency
Display current set frequency of the inverter
Range: 0.00Hz~P00.03
●
P17.01
Output
frequency
Display current output frequency of the inverter
Range: 0.00Hz~P00.03
●
P17.02
Ramp
reference
frequency
Display current ramp reference frequency of the
inverter
Range: 0.00Hz~P00.03
●
P17.03
Output
voltage
Display current output voltage of the inverter
Range: 0~1200V
●
P17.04
Output
current
Display current output current of the inverter
Range: 0.0~3000.0A
●
P17.05 Motor speed
Display the rotation speed of the motor.
Range: 0~65535RPM
●
P17.08 Motor power
Display current motor power
Range:-300~300%
●
P17.09
Output
torque
Display the current output torque of the inverter.
Range: -250.0~250.0%
●
P17.10
Evaluated
motor
frequency
Evaluated frequency of motor rotor
Range: 0.00Hz~ P00.03
●
P17.11
DC bus
Display current DC bus voltage of the inverter
●