Goodrive200A
inverters Function parameters
71
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
numbers and stop to recount before the next
pulse.
The setting counting value P08.26 should be no
more than the setting counting value P08.25.
The function is illustrated as below:
Setting range of P08.25:P08.26~65535
Setting range of P08.26:0~P08.25
P08.27
Set running
time
Pre-set running time of the inverter. When the
accumulative running time achieves the set time,
the multi-function digital output terminals will
output the signal of “running time arrival”.
Setting range:0~65535 min
0m
○
P08.28
Fault reset
times
The time of the fault reset: set the fault reset time
by selecting this function. If the reset time
exceeds this set value, the inverter will stop for
the fault and wait to be repaired.
The interval time of the fault reset: The interval
between the time when the fault occurs and the
time when the reset action occurs.
Setting range of P08.28:0~10
Setting range of P08.29:0.1~3600.0s
0
○
P08.29
Interval time
of automatic
fault reset
1.0s
○
P08.30
Frequency
decreasing
ratio of the
dropping
control
The output frequency of the inverter changes as
the load. And it is mainly used to balance the
power when several inverters drive one load.
Setting range:0.00~10.00Hz
0.00Hz
○
P08.32
FDT1
electrical
level
detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
the multi-function digital output terminals will
output the signal of “frequency level detect FDT”
until the output frequency decreases to a value
lower than (FDT electrical level—FDT retention
detection value) the corresponding frequency,
the signal is invalid. Below is the waveform
diagram:
50.00
Hz
○
P08.33
FDT1
retention
detection
value
5.0%
○
P08.34
FDT2
50.00
○