Goodrive200A
inverters Function parameters
30
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00.02
Communicati
on selection
0: MODBUS communication
1~3: Reserved
0
○
P00.03
Max. output
frequency
This parameter is used to set the Maximum
output frequency of the inverter. Users should
pay attention to this parameter because it is the
foundation of the frequency setting and the
speed of acceleration and deceleration.
Setting range: P00.04~400.00Hz
50.00
Hz
◎
P00.04
Upper limit of
the running
frequency
The upper limit of the running frequency is the
upper limit of the output frequency of the inverter
which is lower than or equal to the maximum
frequency.
Setting range:P00.05~P00.03 (Max. output
frequency)
50.00
Hz
◎
P00.05
Lower limit of
the running
frequency
The lower limit of the running frequency is that of
the output frequency of the inverter.
The inverter runs at the lower limit frequency if
the set frequency is lower than the lower limit
one.
Note:
Max. output frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range:0.00Hz~P00.04 (Upper limit of the
running frequency)
0.00Hz
◎
P00.06
A frequency
command
0:Keypad data setting
Modify the value of P00.10 (set the frequency by
keypad) to modify the frequency by the keypad.
1:Analog AI1 setting(The inverter(
≤
15kW) can
be set by the analog potentiometer on the keypad
and AI1 setting is not available for the device
which is 18.5kW or higer than 18.5kW)
2:Analog AI2 setting
3:Analog AI3 setting
Set the frequency by analog input terminals.
Goodrive200A series inverters provide 3
channels analog input terminals as the standard
configuration, of which AI1/AI2 are the
voltage/current option (0~10V/0~20mA) which
can be shifted by jumpers; while AI3 is voltage
input (-10V~+10V).
Note:
when analog AI1/AI2 select 0~20mA input,
the corresponding voltage of 20mA is 10V.
0
○
P00.07
B frequency
command
2
○