Goodrive200A
inverters Function parameters
39
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
during
powering on
of the running terminal during powering on.
0: The terminal running command is invalid when
powering on. Even the running command is
detected to be valid during powering on, the
inverter won’t run and the system keeps in the
protection state until the running command is
canceled and enabled again.
1: The terminal running command is valid when
powering on. If the running command is detected
to be valid during powering on, the system will
start the inverter automatically after the
initialization.
Note:
this function should be selected with
cautions, or serious result may follow.
P01.19
Action
selection
(operation
frequency<lo
wer
frequency
limit and valid
when the
lower
limit >0)
This function code determines the running state
of the inverter when the set frequency is lower
than the lower-limit one.
0: Run at the lower limit frequency
1: Stop
2: Hibernation
The inverter will coast to stop when the set
frequency is lower than the lower-limit one. If the
set frequency is above the lower limit one again
and it lasts for the time set by P01.20, the inverter
will come back to the running state automatically.
0
◎
P01.20
Hibernation
restore delay
time
This function code determines the hibernation
delay time. When the running frequency of the
inverter is lower than the lower limit one, the
inverter will pause to stand by.
When the set frequency is above the lower limit
one again and it lasts for the time set by P01.20,
the inverter will run automatically.
Note:
The time is the total value when the set
frequency is above the lower limit one.
Setting range: 0.0~3600.0s
(valid when P01.19=2)
0.0s
○
P01.21
Restart after
power off
This function can enable the inverter start or not
after the power off and then power on.
0
○