Goodrive200A
inverters Function parameters
52
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
BIT6:S7
virtual terminal
BIT7:S8
virtual terminal
BIT8:HDI
virtual terminal
P05.13
Terminals
control
running
mode
Set the operation mode of the terminals control
0:2-wire control 1, comply the enable with the
direction. This mode is widely used. It determines
the rotation direction by the defined FWD and
REV terminals command.
FWD
REV
COM
K1
K2
运行命令
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
停止
保持
正转运行
反转运行
1:2-wire control 2; Separate the enable from the
direction. FWD defined by this mode is the
enabling ones. The direction depends on the
state of the defined REV.
2:3-wire control 1; Sin is the enabling terminal on
this mode, and the running command is caused
by FWD and the direction is controlled by REV.
Sin is natural closed.
The direction control is as below during
operation:
Sln
REV
Previous
direction
Current
direction
0
◎