Goodrive200A
inverters Function parameters
48
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P04.08
V/F voltage 3
of motor 1
Note:
V1
<
V2
<
V3, f1
<
f2
<
f3. Too high low
frequency voltage will heat the motor excessively
or damage. The inverter may occur the
overcurrent speed or overcurrent protection.
The setting range of P04.03: 0.00Hz~P04.05
The setting range of P04.04:0.0%~110.0%
The setting range of P04.05:P04.03~ P04.07
The setting range of P04.06:0.0%~110.0%
(the rated voltage of motor 1)
The setting range of P04.07:P04.05~ P02.02
(the rated frequency of motor 1)
The setting range of P04.08:0.0%~110.0%
(the rated voltage of motor 1)
00.0%
○
P04.09
V/F slip
compensatio
n gain of
motor 1
This function code is used to compensate the
change of the rotation speed caused by load
during compensation SVPWM control to improve
the rigidity of the motor. It can be set to the rated
slip frequency of the motor which is counted as
below:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor, its
function code is P02.02; n is the rated rotating
speed of the motor and its function code is
P02.03; p is the pole pair of the motor. 100.0%
corresponds to the rated slip frequency
△
f.
Setting range:0.0~200.0%
100.0%
○
P04.10
Motor 1 low
frequency
vibration
control factor
In the SVPWM control mode, current fluctuation
may occur to the motor on some frequency,
especially the motor with big power. The motor
can not run stably or overcurrent may occur.
These phenomena can be canceled by adjusting
this parameter.
The setting range of P04.10:0~100
The setting range of P04.11:0~100
The setting range of P04.12:0.00Hz~P00.03
(the Max. frequency)
10
○
P04.11
Motor 1 high
frequency
vibration
control factor
10
○
P04.12
Motor 1
vibration
control
threshold
30.00 Hz
○
P04.26
Energy-savin
g operation
selection
0:No action
1:Automatic energy-saving operation
Motor on the light load conditions, automatically
0
◎