Goodrive200A
inverters Function parameters
45
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
torque
source
analog potentiometer on the keypad and AI1
setting is not available for the device which is
18.5kW or higer than 18.5kW)
2: AI2
3: AI3
4: HDI
5:MODBUS communication
Note
: setting mode 1~9,100% corresponds to
three times of the motor current.
P03.20
Keypad
setting of
electromotion
torque
The function code is used to set the limit of the
torque.
Setting range:0.0~300.0%(motor rated current)
180.0%
○
P03.21
Keypad
setting of
braking
torque
180.0%
○
P03.22
Weakening
coefficient in
constant
power zone
The usage of motor in weakening control.
Function code P03.22 and P03.23 are effective
at constant power. The motor will enter into the
weakening state when the motor runs at rated
speed. Change the weakening curve by
modifying the weakening control coefficient. The
bigger the weakening control coefficient is, the
steeper the weak curve is.
The setting range of P03.22:0.1~2.0
The setting range of P03.23:10%~100%
0.3
○
P03.23
Lowest
weakening
point in
constant
power zone
20%
○
P03.24
Max. voltage
limit
P03.24 set the Max. Voltage of the inverter, which
is dependent on the site situation.
The setting range:0.0~120.0%
100.0%
◎
P03.25
Pre-exciting
time
Reactivate the motor when the inverter starts up.
Build up a magnetic field inside the inverter to
improve the torque performance during the
starting process.
0.300s
○