Goodrive200A
inverters Installation guidelines
13
Environment
Conditions
The maximum relative humility should be equal to or less than
60% in corrosive air.
Storage
temperature
-30~+60
℃
Running
environment
condition
The installation site of the inverter should:
keep away from the electromagnetic radiation source;
keep away from contaminative air, such as corrosive gas, oil mist
and flammable gas;
ensure foreign objects, such as metal power, dust, oil, water can
not enter into the inverter(do not install the inverter on the
flammable materials such as wood);
keep away from direct sunlight, oil mist, steam and vibration
environment.
Altitude
Below 1000m
If the sea level is above 1000m, please derate 1% for every
additional 100m.
Vibration
≤
5.8m/s
2
(0.6g)
Installation direction
The inverter should be installed on an upright position to ensure
sufficient cooling effect.
Note:
Goodrive200A series inverters should be installed in a clean and ventilated
environment according to enclosure classification.
Cooling air must be clean, free from corrosive materials and electrically conductive
dust.
4.2.2 Installation direction
The inverter may be installed on the wall or in a cabinet.
The inverter must be installed in an upright position. Check the installation site according to
the requirements below.
Refer to chapter
Dimension Drawings
in the appendix for frame
details.
Fig 4-1 Installation direction of the inverter