Goodrive200A
inverters Function parameters
38
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Setting range of P01.10: 0.00~50.00s
Setting range of P01.11: 0.0~100.0%
Setting range of P01.12: 0.00~50.00s
P01.13
Dead time of
FWD/REV
rotation
During the procedure of switching FWD/REV
rotation, set the threshold by P01.14, which is as
the table below:
Setting range: 0.0~3600.0s
0.0s
○
P01.14
Shifting
between
FWD/REV
rotation
Set the threshold point of the inverter:
0:Switch after 0 frequency
1:Switch after the starting frequency
2:Switch after the stopping speed
0
◎
P01.15
Stopping
speed
0.00~100.00Hz
0.50 Hz
◎
P01.16
Detection of
stopping
speed
0: Detect according to speed setting (no stopping
delay)
1: Detect according to speed feedback (only valid
for vector control)
1
◎
P01.17
Detection
time of the
feedback
speed
If set P01.16 to 1, the feedback frequency is less
than or equal to P01.15 and detect in the set time
of P01.17, the inverter will stop; otherwise the
inverter will stop after the set time of P01.17
Setting range: 0.00~100.00s (only valid when
P01.16=1)
0.50s
◎
P01.18
Operation
protection
When the running command channel is the
terminal control, the system will detect the state
0
○