Goodrive300-21 integrated machine for air compressor
Function description
-
45
-
Function
code
Name
Description
Default Modify
P14.07
Communication
address of auxiliary
fan
1
–247; 0 indicates a broadcast address
1
○
P15.00
Auxiliary pressure
start-up protection
0: Disable
1: Enable
0
◎
P15.01
Auxiliary pressure
start-up protection
setting value
0.00
–20.00MPa
The inverter cannot start if current auxiliary
pressure (P19.20) is greater than auxiliary
pressure start-up protection value (P15.01).
0.30MPa
○
P15.02
Stop delay time of
auxiliary pressure
start-up protection
0
–300s
When
the
auxiliary
pressure
start-up
protection (P15.00=1) is turned on, if the
current auxiliary pressure is still greater than
the set value of P15.01 after the stop time
delay (P18.14), the inverter will keep running
at idle frequency and stop running after the
delay time of P15.02.
P18.12
P18.14
P15.02
Frequency
Time
30s
○
P15.03
Pressure limit after
the time threshold
reached
0.00
–P18.04MPa
When the accumulated running time of the
device (P19.16) reaches the set value of
P15.04, the pressure cannot exceed the value
of P15.03.
0.50MPa
○
P15.04
Upper limit of
accumulated device
running time
0
–65535h
Note:
P15.03 is invalid when P15.04 is set to
0.
0
○
P15.05
Device status flag
Bit0: High auxiliary pressure flag
0: None
1: Auxiliary pressure is high. The device is not
allowed to start.
Bit1: Limited max. set pressure flag
0: None
1: Function limited. Please contact the
manufacturer.
0
●