Goodrive300-21 integrated machine for air compressor
Installation guidance
-
8
-
Symbol
Name
Remarks
CN8
110V voltage selection
terminal
Select this terminal with jumpers when users select the
solenoid valve with 110V coil or the contactor.
J5
Access terminal for 485
communication terminal
resistor
485 corresponds to access terminal resistor. Does not
connect terminal resistor by default.
J6
Short-circuit terminal of
PE and GND
ON corresponds to short-circuit. No short circuit by default
J7
Jumper terminal
Corresponds to P1+, P1- pressure analog signal selection. I
corresponds to current signal, V to voltage signal. The
default is current input signal.
J8
Jumper terminal
Corresponds to P2+, P2- pressure analog signal selection. I
corresponds to current signal, V to voltage signal. The
default is current input signal.
J9
PE/CGND selection
terminal
485 communication is non-isolation mode. CN14-5 is short
circuited with PE by default.
SW1
DIP switch
Set to +24V terminal by default. See details at Figure 2-5
●
●
●
COM
+24V
PW
COM
+24V
•
•
S1
S2
•
SW1
COM
+24V
PW
COM
+24V
•
•
S1
S2
•
●
●
●
+24V
SW1
Figure 2-5 Internal power (NPN mode)
Figure 2-6 External power (PNP mode)
When digital input adopts in24V, set the toggle switch according to Figure 2-5 and short circuit
+24V with PW. When digital input adopts ex24V, set the toggle switch according to Figure 2-6
and short circuit COM with PW.