Goodrive300-21 integrated machine for air compressor
Function description
-
59
-
Function
code
Name
Description
Default Modify
1: Pressure pre-alarm; 0: normal
BIT8: Auxiliary temperature pre-alarm signal
1: Temperature pre-alarm; 0: normal
BIT9: Auxiliary pressure alarm signal
1: Pressure alarm; 0: normal
BIT10: Auxiliary temperature alarm signal
1: Temperature pre-alarm; 0: normal
BIT11: Maintenance time-out reminder
1: maintenance time-out reminder; 0: normal
BIT12: Phase sequence reminder
1: Fault; 0: normal
P19.15
Device state
0: Stand-by
1: Run
2: Faulty
3: Emergency-stop
4: Under-voltage
5: Alarm
6: Sleep
7: Stop
8: Restart delay
0
●
P19.16
Accumulated
running time of the
device
Range: 0
–65535h
0
●
P19.17
Accumulated
loading running time
0
●
P19.18
Restart count down
It displays the residue time of restart delay.
The system enters restart delay state and
restart count down after stop to prevent restart
immediately. After restart delay time is
passed, the system enters stand-by state and
it can receive starting command in stand-by
state.
Range: 0
–3600s
0s
●
P19.19
Temperature PID
output value
It displays the output value of head
temperature PID control adjustment. 100.00%
corresponds to the maximum output
frequency P00.03 of the fan.
Range: 0.00
–100.00%
0.00%
●