Function description
-
30
-
Function
code
Name
Description
Default Modify
P04.05
V/F frequency point
2 of motor 1
P04.03
–P04.07
00.00Hz
○
P04.06
V/F voltage point 2
of motor 1
0.0%
–110.0% (of the rated voltage of motor 1) 00.0%
○
P04.07
V/F frequency point
3 of motor 1
P04.05
–P02.02 (Rated frequency of motor 1)
/ P04.05
–P02.16 (Rated frequency of motor 1)
00.00Hz
○
P04.08
V/F voltage point 3
of motor 1
0.0%
–110.0% (of the rated voltage of motor 1) 00.0%
○
P04.09
V/F slip
compensation gain
of motor 1
0.0
–200.0%
100.0%
○
P04.10
Low-frequency
oscillation control
factor of motor 1
0
–100
10
○
P04.11
High-frequency
oscillation control
factor of motor 1
0
–100
10
○
P04.12
Oscillation control
threshold of motor 1
0.00Hz
–P00.03 (Max. output frequency)
30.00Hz
○
P04.26
Energy-saving run
0: Disable
1: Automatic energy-saving run
0
◎
P04.33
Weakening
coefficient in
constant power
zone
1.00
–1.30
1.00
○
P04.34
Reactive
closed-loop
proportional
coefficient
0
–3000
100
○
P04.35
Reactive
closed-loop integral
coefficient
0
–3000
20
○
P05.00
Reserved
Reserved
0
◎
P05.01
Function of S1
0: No function
1: Run forward
2: Run reversely
3: Three-wire running control
0
◎
P05.02
Function of S2
0
◎
P05.03
Function of S3
0
◎
P05.04
Function of S4
0
◎