Goodrive300-21 integrated machine for air compressor
Function description
-
50
-
Function
code
Name
Description
Default Modify
inverter will carry out loading operation again
and pressure PID will regulate accordingly.
Manual: set through touch screen or other
communication methods
P18.02
Loading/unloading
mode
0: Automatic
1: Manual
In manual mode, loading/unloading is
conducted manually via touch screen or other
communication methods after air compressor
starts; In automatic mode, load/unloading will
be conducted automatically according to the
pressure after air compressor starts. For
details, see section 5.2.
0
○
P18.03
Temperature sensor
channel
0: head temperature PT1, auxiliary
temperature PT2
1: head temperature PT2, auxiliary
temperature PT1
2: Temperature display in regular inverter
mode (P18.00=0)
(head temperature (P19.12) PT1, auxiliary
temperature (P19.21) PT2)
0
◎
P18.04
Upper limit of
pressure sensor P1
0.00
–20.00Mpa
It is related to actual range of pressure sensor.
The voltage corresponds to P18.04 is P05.34.
Note:
This value stays in current set value
during restoring to factory value.
1.60Mpa
◎
P18.05
Unloading pressure In automatic loading/unloading mode, when
air compressor control is valid and air supply
of the compressor becomes normal after it
starts, if exhaust pressure is detected to be
above P18.05, automatic unloading will be
applied. If sleep function is valid (P18.01=1),
the inverter enters sleep state; when exhaust
pressure is detected to be below P18.06,
automatic loading will be applied. P18.07 is
used to set the air supply pressure when air
compressor operation is stable. During
loading operation, the rotation speed of the
0.80Mpa
○
P18.06
Loading pressure
0.60Mpa
○
P18.07
Set pressure
0.70Mpa
○