ABK2027IQE01_A - Installation and Operation Manual
FCC Part 15 B (class A) EMC tests
IEEE 1547.1
TM
IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Resources with Electric
Power Systems.
2.8. EMC requirements
These units are equipped with the necessary filtering elements to comply with EMC requirements for industrial
applications in order to prevent disturbances in other equipment outside the installation.
All of these units are connected to the grid through a low to medium voltage transformer. This transformer gives
the unit galvanic isolation that affects its good performance in terms of noise emission (see Section
CAUTION
Any auxiliary element must be connected to the low voltage network powering the units via a galvanic isolation
transformer (see Section
“6.8.2. Auxiliary transformer”
The maximum distance between the units and the grid connection transformer must be less than 30 meters.
2.9. Protection class
These units meet NEMA 3R degree of protection against external agents, so can be installed outdoors.
They include standard protection covers for sand/dust storms for the front and rear grilles.
2.10. Pollution degree
The pollution degree for which the units have been designed is grade 3.
Suitable measures should be taken to provide dust-free air of sufficient quality in the vicinity of the inverter.
2.11. Acoustic contamination
When on, the inverter generates a buzzing sound.
Do not place it in an occupied room, or on light supports which might amplify this buzz. The mounting surface
must be firm and appropriate for the weight of the unit.
30
Unit description
Ingeteam
Summary of Contents for INGECON SUN 1000TL U B360
Page 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Page 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Page 176: ...Notes...
Page 177: ...Notes...
Page 178: ...Notes...
Page 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...