ABK2027IQE01_A - Installation and Operation Manual
Phase connection via two terminals with two holes
A
B
D
C
C
B
E
13/4 in
≤
0.39 in
≤
1.3 in
M12
M12
A. M12 DIN 933 screw.
B. M12 NFE-25 511 M washer.
C. Terminal. Diameter of the M12 hole, maximum thickness of 0.39 in (10 mm), maximum width of 1.3 in
(33 mm), vertical distance between holes of 13/4 in (44.5 mm).
D. Busbar.
E. M12 DIN 934 nut.
Neutral connection via a terminal with one hole
A
B
D
C
≤
0.39 in
≤
1.3 in
M6
A. M6 DIN 934 nut.
B. M6 NFE-25 511 M washer.
C. Terminal. Hole diameter of M6, maximum thickness of 0.39 in (10 mm), maximum width of 1.3 in
(33 mm).
D. Busbar.
16.4.2. AC phases connection process via a terminal
Proceed in the following order for each phase:
1. Clean the contact surfaces on both the terminal and the busbar with a clean cloth and ethanol.
114
AC connection
Ingeteam