ABK2027IQE01_A - Installation and Operation Manual
3L Mechanical specifications
max. 5.12 in (130 mm)
max. 6.85 in (174 mm)
max. 5.28 in (134 mm)
max. 2.91 in (74 mm)
max. 2.91 in (74 mm)
max. 0.24 in (6 mm)
max. 8.07 in (205 mm)
These inverters can be equipped with fuse holders from different manufacturers, that is why in the previous figure
they indicate as reference the minimum measures of the fuse holders that can be used.
Approval references
CAUTION
For continuous fire risk protection, only replace with the same fuse.
The following fuse references meet the required electrical and mechanical specifications.
Bussmann
Fuse holder base size
Fuse size
Rated current
Rated voltage
PV-63A-01XL
2XL, 3L
01
63 A
1000 VDC
PV-80A-01XL
80 A
PV-100A-01XL
100 A
PV-125A-01XL
125 A
PV-160A-01XL
160 A
PV-200A-1XL
1
200 A
PV-200A-2XL
2
200 A
PV-250A-2XL
250 A
PV-315A-2XL
315 A
PV-350A-3L
3L
3
350 A
PV-400A-3L
400 A
PV-500A-3L
500 A
PV-630A-3L
630 A
52
Preparation for installing the unit
Ingeteam
Summary of Contents for INGECON SUN 1000TL U B360