ABK2027IQE01_A - Installation and Operation Manual
2.17. Configuration parameters
DC inputs
750TL U B270
830TL U B300
1000TL U B360
1110TL U B400
1140TL U B410
Range of operating input voltage
397 ~ 820 V
440 ~ 820 V
524 ~ 820 V
580 ~ 820 V
595 ~ 820 V
Maximum input voltage
1.050 V
Maximum input current
2.000 A
Maximum short circuit input current
3.000 A
Maximum source feedback current
0 A
AC output
750TL U B270
830TL U B300
1000TL U B360
1110TL U B400
1140TL U B410
Outgoing power factor
> 0.99 (adjustable 0 ~ 1)
Voltage range (AC) (L-L)
238 ~ 324 V
264 ~ 360 V
317 ~ 432 V
352 ~ 480 V
360.8 ~ 492 V
Range of operating frequency
57 ~ 60.5 Hz
Number of phases
3
Nominal output voltage (AC)
270 V
300 V
360 V
400 V
410 V
Normal output frequency
60 Hz
Maximum AC output current per line @ 95 ºF
(35 ºC)/ @ 122 ºF (50 ºC)
1.600 A / 1.472 A
Power @ 95 ºF (35 ºC)/ @ 122 ºF (50 ºC)
748.3 kW / 688.4 kW
831.4 kW / 764.9 kW
997.7 kW / 917.8 kW
1108.5 kW /
1019.8 kW
1136 kW / 1046 kW
Maximum (AC) current fault and duration
3.440 A @ 11 ms
Maximum overcurrent protection
1.600 A
Reconnection time
1 ~ 5 minutes
Normal temperature range of use
-4 ºF (-20 ºC) ~ 140 ºF (60 ºC)
Maximum temperature at a maximum power
@ 1,600 A / @ 1,472 A
up to 95 ºF (35 ºC) / up to 122 ºF (50 ºC)
Housing protection
NEMA 3R
DC inputs
1165TL U B420
1190TL U B430
1220TL U B440
1250TL U B450
1275TL U B460
Range of operating input voltage
610 ~ 820 V
623.5 ~ 820 V
638 ~ 820 V
652 ~ 820 V
666 ~ 820 V
Maximum input voltage
1.050 V
Maximum input current
2.000 A
Maximum short circuit input current
3.000 A
Maximum source feedback current
0 A
AC output
1165TL U B420
1190TL U B430
1220TL U B440
1250TL U B450
1275TL U B460
Outgoing power factor
> 0.99 (adjustable 0 ~ 1)
Voltage range (AC) (L-L)
369.6 ~ 504 V
378.4 ~ 516 V
387.2 ~ 528 V
396 ~ 540 V
404.8 ~ 552 V
Range of operating frequency
57 ~ 60.5 Hz
Number of phases
3
Nominal output voltage (AC)
420 V
430 V
440 V
450 V
460 V
Normal output frequency
60 Hz
Maximum AC output current per line @ 95 ºF
(35 ºC)/ @ 122 ºF (50 ºC)
1.600 A / 1.472 A
Power @ 95 ºF (35 ºC)/ @ 122 ºF (50 ºC)
1163.9 kW /
1070.8 kW
1192 kW / 1097 kW
1217 kW / 1122 kW
1247 kW / 1147 kW
1275 kW / 1173 kW
Maximum (AC) current fault and duration
3.440 A @ 11 ms
Maximum overcurrent protection
1.600 A
Reconnection time
1 ~ 5 minutes
Normal temperature range of use
-4 ºF (-20 ºC) ~ 140 ºF (60 ºC)
Maximum temperature at a maximum power
@ 1,600 A / @ 1,472 A
up to 95 ºF (35 ºC) / up to 122 ºF (50 ºC)
Housing protection
NEMA 3R
34
Unit description
Ingeteam
Summary of Contents for INGECON SUN 1000TL U B360
Page 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Page 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Page 176: ...Notes...
Page 177: ...Notes...
Page 178: ...Notes...
Page 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...